Sanyo 85464359981002 Air Purging, Manifold gauge, Vacuum pump, Leak test, previous page, Fig

Models: 85464359981002

1 90
Download 90 pages 27.37 Kb
Page 65
Image 65
7. AIR PURGING

7. AIR PURGING

Air and moisture in the refrigerant system may have undesirable effects as indicated below.

pressure in the system rises

operating current rises

cooling (or heating) efficiency drops

moisture in the refrigerant circuit may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant system

Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system.

Air Purging with a Vacuum Pump (for Test Run) Preparation

Check that each tube (both liquid and gas tubes) between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed. Remove the valve caps from both the gas tube and liquid tube service valves on the outdoor unit. Note that both liquid and gas tube service valves on the outdoor unit are kept closed at this stage.

Manifold gauge

Fig. 7-1

Vacuum pump

Outlet

Inlet

Fig. 7-2

Manifold valve

Leak test

(1)Attach a manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.

CAUTION

Use a manifold valve for air

purging. If it is not available, use

 

 

 

a stop valve for this purpose. The

 

“Hi” knob of the manifold valve

 

must always be kept closed.

(2)Pressurize the system to no more than

512 psig (36 kgf/cm2G) with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 512 psig (36 kgf/cm2G). Then, test for leaks with liquid soap.

CAUTION

To avoid nitrogen entering the

refrigerant system in a liquid state,

 

 

 

the top of the cylinder must be

 

higher than the bottom when you

 

pressurize the system. Usually,

 

the cylinder is used in a vertical

 

standing position. (Refer to the

 

previous page.)

Pressure gauge

Gas tube

Liquid tube

Lo Manifold gauge Hi

Charge hose

Cylinder valve

Vacuum pump Nitrogen gas cylinder (In vertical standing position)

Service port ø5/16"

Open

Close

Outdoor unit

Open

Close

Fig. 7-3

65

Page 65
Image 65
Sanyo 85464359981002 Air Purging, Manifold gauge, Vacuum pump, Leak test, Use a manifold valve for air, previous page, Fig