(3)To mount the indoor unit on the rear panel.
1.When installing the indoor unit, position the indoor unit onto the installation tabs on the upper part of the rear panel. (Fig.
2.Press on the air outlet to hold it in place, and press the lower part of the indoor unit until a “click” sound is heard and the indoor unit is securely fastened to the installation tabs on the lower side of the rear panel. (Fig.
Raising the clamp to lift up the indoor unit will facilitate this work. (Fig.
To remove the indoor unit, press up on the 2 locations
(▲ marks) on the lower part of the unit frame to disconnect the installation tabs. Refer to Section
Then lift up the indoor unit to remove it.
3-34. Shaping the Tubing
Press
Fig.
Clamp
Right-rear tubing
(1)Shape the refrigerant tubing so that it can easily go into the hole. (Fig.
(2)After performing a leak test, wrap both the refrigerant tubing and drain hose together with insulating tape.
The drain hose should be positioned below the refrigerant tubes, and should be given sufficient space so that no strong tension is applied to it.
K | (3) Push the wiring, refrigerant tubing and drain hose through the hole | |
in the wall. Adjust the indoor unit so it is securely seated on the | ||
|
Fig.
Rear panel tab
Insulating
tape
Plastic cover
Refrigerant
tubing
Indoor and outdoor unit connection wiring
rear panel. |
Left or left-rear tubing
(1)Pass the tubing and drain hose into the rear of the indoor unit. Provide sufficient length for the connections to be made. Next, bend the tubing with a pipe bender, and connect them.
(2)After performing a leak test, wrap the refrigerant tubing and drain hose together with insulating tape, as shown in the figure at right. (Fig.
Then fit the tubing into the tubing storage space in the rear of the indoor unit and clamp in place.
(3)Adjust the indoor unit so that it is securely installed onto the rear panel.
3-35. Installing the Drain Hose
a)The drain hose should be slanted downward to the outside. (Fig.
b)Never form a trap in the course of the hose.
c)If the drain hose will run in the room, insulate the hose* so that chilled condensation will not damage furniture or floors.
*Foamed polyethylene or its equivalent is recommended.
WARNING | Do not supply power to the unit or operate | |
it until all tubing and wiring to the outdoor | ||
| ||
| ||
| unit are completed. |
Fig.
Insulation
Fig.
Refrigerant tubing
Insulating tape | Rear panel |
Drain hose
Fig.
Indoor unit
Slant
Refrigerant tubing
Fig.
54