Schneider Electric XPSMF2DO801 manual Internal, Convection, Housing, Variable Description

Models: XPSMF2DO801

1 82
Download 82 pages 20.26 Kb
Page 20
Image 20

Overview

Internal

With internal heat convection, the heat is dissipated outside through the walls of the

Convection

housing. This is possible when the ambient temperature is lower than that inside the

 

housing.

 

 

The following table describes the variables used to calculate the internal convection:

 

 

 

 

Variable

Description

 

 

 

 

Pv [W]

heat output (heat dissipation) of the electronic components

 

 

 

 

A [m2]*

effective surface area of the housing

 

k [W/m2 K]*

the housing heat transfer coefficient

 

 

(e.g., Steel sheet: approximately 5.5 W/m2 K)*

* (1m2 = 10.76ft2)

The maximum temperature increase of all electronic devices inside the housing is calculated as follows:

(∆ ) Pv

T max = ------------

k A

The power dissipation Pv can be calculated based on the values of the electrical power of the controller, its inputs, and outputs.

20

33003405 07/2007

Page 20
Image 20
Schneider Electric XPSMF2DO801 manual Internal, Convection, Housing, Variable Description