Equipment Description

Connections for SafeEthernet/ Networking Examples

For the networking via SafeEthernet protocol, the devices are equipped - depending on the design - with two connections arranged on the lower side panel of the case. See example of a Safety-Related Communication, p. 40.

The various systems can be networked together as required via Ethernet (star or line configuration). A programming unit (PC) can also be connected wherever required.

Note: Ensure that no network loops are formed when connecting systems together. The system must receive data packets along one path only.

Modbus TCP/IP The Modbus serial slave field bus protocol can communicate with the Modbus TCP/IP protocol via the Ethernet interfaces on the Safety PLC.

Standard Modbus communication transfers the slave address and a CRC checksum in addition to the instruction code and the data. In Modbus TCP/IP the subordinate TCP/IP protocol handles this function.

Note: More information about Modbus TCP/IP protocol can you find in the online help of XPSMFWIN.

Used Network Ports for Ethernet Communication

UDP ports and usage

UDP Ports

Usage

 

 

8000

programming and operation with XPSMFWIN

 

 

8001

configuration of the remote I/O via PLC

 

 

6010

SafeEthernet

 

 

6005/6012

if TCS_DIRECT was not activated within HH network

 

 

TCP ports and usage

UDP Ports

Usage

 

 

502

Modbus (changeable by user)

 

 

 

 