Equipment Description

Mechanical

The most important test and limit values for mechanical conditions are listed in the

Conditions

following table:

 

 

 

 

 

EN 61131-2

Mechanical Tests

 

 

 

 

 

Vibration test, operating: 5 Hz to 9 Hz / 3.5 mm, 9 Hz to

 

 

150 Hz / 1g

 

 

 

 

6.3.5.1

Immunity vibration test: 10 Hz to 150 Hz, 1 g, EUT

 

 

operating, 10 cycles per axis

 

 

 

 

6.3.5.2

Immunity shock test: 15g, 11ms, EUT operating, 2 cycles

 

 

per axis

 

 

 

 

 

 

 

 

 

 

 

 

EMC Conditions

The most important tests and limit values for EMC conditions are listed in the

 

following tables:

 

 

 

 

 

EN 61131-2

Noise Immunity Test

 

 

 

 

6.3.6.2.1 IEC/EN 61000-4-2

ESD test: 4 kV contact/ 8 kV air discharge

 

 

 

 

6.3.6.2.2 IEC/EN 61000-4-3

RFI test (10 V/m): 26 MHz to 1 GHz, 80% AM

 

 

 

 

6.3.6.2.3 IEC/EN 61000-4-4

Burst test: 2 kV power supply / 1 kV signal lines

 

 

 

 

6.3.6.2.4 IEC/EN 61000-4-12

Damped oscillatory wave immunity test: 1 kV

 

 

 

 

 

 

 

IEC/EN 61000-6-2

Noise Immunity Test

 

 

 

 

IEC/EN 61000-4-6

Radio frequency common mode: 10 V

 

 

150 kHz to 80 MHz, AM

 

 

 

 

IEC/EN 61000-4-3

900 MHz pulses

 

 

 

 

IEC/EN 61000-4-5

Surge: 1 kV, 0.5 kV

 

 

 

 

 

 

 

IEC/EN 61000-6-4

Noise Emission Test

 

 

 

 

EN50011 Class A

Emission test: radiated, conducted

 

 

 

 

 

 

 

 

 

 

 

 