Brief description of the functional devices

 

 

 

 

 

 

 

 

System signal

R/W

Meaning

 

 

 

 

 

 

 

 

DO[xx].Error Code [BYTE]

W

error codes of the digital output channels

 

 

 

 

 

 

 

 

 

 

 

 

0x01

error in digital output module

 

 

 

 

 

0x04

error reading back the digital outputs

 

 

 

 

 

0x10

error reading back relay [x].1

 

 

 

 

 

 

(the channel is permanently deactivated)

 

 

 

 

 

0x20

error reading back relay [x].2

 

 

 

 

 

 

(the channel is permanently deactivated)

 

 

 

 

 

0x080

channel still can not be activated after deactivation by

 

 

 

 

 

 

￿

application

 

 

 

 

 

 

￿

forcing

 

 

 

 

 

 

￿

channel/module failure

 

 

 

 

 

 

 

DO[xx].Value [BOOL]

W

output value of digital output channels

 

 

 

 

 

 

 

 

 

 

 

 

0

output power-free

 

 

 

 

 

1

output activated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33003405 07/2007

69

Page 69
Image 69
Schneider Electric XPSMF2DO801 manual Brief description of the functional devices