Equipment Description

Operating Conditions

Overview

The XPSMF2DO801 safety remote output module has been developed in

 

compliance with the requirements of the following standards for EMC, climate and

 

environment:

 

 

 

 

 

IEC 61131-2

Programmable Controllers, Part 2, Equipment Requirements and

 

 

Tests

 

 

 

 

IEC 61000-6-2

EMC Generic Standards, Part 6-2

 

 

 

 

IEC 61000-6-4

EMC General Emission Standard, Industrial Environment

 

 

 

To use the XPSMF2DO801 safety remote output module, the following conditions must be fulfilled:

 

Protection Class

Protection class II according to IEC/EN 61131-2

 

 

 

 

Pollution

Pollution degree II

 

 

 

 

Altitude

< 2000 m / 6561.7 ft

 

 

 

 

Enclosure

Standard: IP 20 If requested by the relevant application standards

 

 

(e.g., EN 60204, EN 954-1), the device must be installed in a required

 

 

enclosure (e.g., IP 54).

 

 

 

 

 

 

 

 

 

 

 

 

Climatic

The most important tests and limit values for climatic conditions are listed in the

Conditions

following table:

 

 

 

 

 

EN 61131-2

Climatic Tests

 

 

 

 

 

Operating temperature: 0°C to 60°C / 32°F to 140°F

 

 

(Test limits -10°C to +70°C / 14°F to 158°F)

 

 

 

 

 

Storage temperature: -40°C to 85°C / -40°F to 185°F (with battery

 

 

only -30°C / -22°F)

 

 

 

 

6.3.4.2

Dry heat and cold withstand test: 70°C / -25°C (158°F / -13°F, 96 h,

 

 

EUT power supply disconnected

 

 

 

 

6.3.4.3

Change of temperature, withstand and immunity test: -25°C / 70°C

 

 

(-13°F / 158°F) and 0°C / 55°C (32°F / 131°F), EUT power supply

 

 

disconnected

 

 

 

 

6.3.4.4

Cyclic damp heat withstand test: 25°C / 55°C (77°F / 131°F), 95%

 

 

relative humidity, EUT power supply disconnected

 

 

 

 

 

 

 

 

 

 

 

 

56

33003405 07/2007

Page 56
Image 56