Brief description of the functional devices
Error Codes
Description of | The error codes listed in this section appear in XPSMFWIN programming | |||
Error Codes | environment. |
| ||
| The following table describes error codes of relay outputs: | |||
|
|
|
|
|
System signal |
| R/W | Meaning |
|
|
|
|
| |
Module.SRS [UDINT] |
| R | slot number | |
|
|
|
| |
Module.Type [UINT] |
| R | type of module, setpoint: 0x003C [60dez] | |
|
|
| ||
Module.Error Code [WORD] | R | error codes of the module | ||
|
|
|
|
|
|
|
| 0x0000 | I/O processing, may be faulty, see further error codes |
|
|
| 0x0001 | no I/O processing (CPU not in RUN) |
|
|
| 0x0002 | no I/O processing during |
|
|
| 0x0004 | manufacturer interface in operation |
|
|
| 0x0010 | no I/O processing: incorrect configuration |
|
|
| 0x0020 | no I/O processing: error rate exceeded |
|
|
| 0x0040 | no I/O processing: configured module not inserted |
|
|
| 0x0080 |
|
|
|
|
|
|
DO.Error Code [WORD] |
| R | error codes of all digital outputs | |
|
|
|
|
|
|
|
| 0x0001 | module error |
|
|
| 0x0002 | MEZ test, safety switch 1 failed |
|
|
| 0x0004 | MEZ test, safety switch 2 failed |
|
|
| 0x0008 | FTZ test of test pattern failed |
|
|
| 0x0010 | MEZ test of readback channels failed |
|
|
| 0x0020 | MEZ test, active disconnection failed |
|
|
| 0x0040 | error with initialization: relays |
|
|
| 0x0080 | FTZ test: error of relay voltage |
|
|
| 0x0100 | FTZ test of CS (chip select) signals failed |
|
|
| 0x0400 | FTZ test: 1. temperature threshold exceeded |
|
|
| 0x0800 | FTZ test: 2. temperature threshold exceeded |
|
|
| 0x1000 | MEZ test: status of safety switch 1 |
|
|
| 0x2000 | MEZ test: status of safety switches |
|
|
| 0x4000 | MEZ test: active disconection by watchdog failed |
|
|
|
|
|
68 | 33003405 07/2007 |