Brief description of the functional devices

Error Codes

Description of

The error codes listed in this section appear in XPSMFWIN programming

Error Codes

environment.

 

 

The following table describes error codes of relay outputs:

 

 

 

 

 

System signal

 

R/W

Meaning

 

 

 

 

 

Module.SRS [UDINT]

 

R

slot number (System-Rack-Slot)

 

 

 

 

Module.Type [UINT]

 

R

type of module, setpoint: 0x003C [60dez]

 

 

 

Module.Error Code [WORD]

R

error codes of the module

 

 

 

 

 

 

 

 

0x0000

I/O processing, may be faulty, see further error codes

 

 

 

0x0001

no I/O processing (CPU not in RUN)

 

 

 

0x0002

no I/O processing during start-up tests

 

 

 

0x0004

manufacturer interface in operation

 

 

 

0x0010

no I/O processing: incorrect configuration

 

 

 

0x0020

no I/O processing: error rate exceeded

 

 

 

0x0040

no I/O processing: configured module not inserted

 

 

 

0x0080

 

 

 

 

 

 

DO.Error Code [WORD]

 

R

error codes of all digital outputs

 

 

 

 

 

 

 

 

0x0001

module error

 

 

 

0x0002

MEZ test, safety switch 1 failed

 

 

 

0x0004

MEZ test, safety switch 2 failed

 

 

 

0x0008

FTZ test of test pattern failed

 

 

 

0x0010

MEZ test of readback channels failed

 

 

 

0x0020

MEZ test, active disconnection failed

 

 

 

0x0040

error with initialization: relays

 

 

 

0x0080

FTZ test: error of relay voltage

 

 

 

0x0100

FTZ test of CS (chip select) signals failed

 

 

 

0x0400

FTZ test: 1. temperature threshold exceeded

 

 

 

0x0800

FTZ test: 2. temperature threshold exceeded

 

 

 

0x1000

MEZ test: status of safety switch 1

 

 

 

0x2000

MEZ test: status of safety switches

 

 

 

0x4000

MEZ test: active disconection by watchdog failed

 

 

 

 

 

68

33003405 07/2007

Page 68
Image 68