Equipment Description
Signal Line Connectors 2
Connection diameters, multiple lead connections (2 leads max, same diameters) | |
|
|
Without lead end sleeves | Solid 0.14 to 0.5 mm2 |
| AWG |
| Stranded 0.14 to 0.75 mm2 |
| AWG |
|
|
Stranded with lead and sleeves (without | 0.25 to 0.34 mm2 |
plastic sleeves) | AWG 22 |
|
|
Stranded with lead end sleeves (with plastic | 0.5 mm2 |
sleeves) | AWG 20 |
|
|
Stripping Length and Torque
| Stripping length | 9 mm (0.35 in) |
|
|
|
|
|
| Torque | 0.22 to 0.25 Nm (1.9 to 2.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Technical Data The XPSMF2DO801 safety remote output device technical data are presented in the following tables:
Interface Ethernet | |
|
|
Operating Voltage | 24 VDC |
| with protective separation, conforming to IEC |
| requirements |
|
|
Current Consumption | max. 0.6 A |
|
|
Operation Temperature | 0 to 60°C / 32°F to 140°F |
|
|
Storage Temperature | |
|
|
Fuse (external) | 10 A (Slow blow) |
|
|
Battery backup | none |
|
|
Protection | IP 20 |
|
|
Max dimensions | width: 207 mm / 8.15 in. (with housing screws) |
| height: 114 mm / 4.49 in. (with latch) |
| depth: 86 mm / 3.39 in. (with grounding bolt) |
|
|
Weight | 1.3 kg / 2.87 lb |
|
|