Schneider Electric XPSMF2DO801 LED Description, Following table describes behaviors of the LEDs

Models: XPSMF2DO801

1 82
Download 82 pages 20.26 Kb
Page 45
Image 45

Equipment Description

LED Description

The following table describes behaviors of the LEDs:

 

 

 

 

 

 

LED

Color

 

Status

Meaning

 

 

 

 

 

Relay Contact

Orange

On

An Output signal is being sent.

Outputs 1-8

 

 

 

 

 

 

 

 

 

 

24 VDC

Green

 

On

24 V DC operating voltage present

 

 

 

 

 

 

 

Not illuminated

Off

No operating voltage

 

 

 

 

 

RUN

Green

 

On

Normal state of PES (RUN) A loader user program is executed (not in

 

 

 

 

 

remote I/O modules). The CPU reads inputs, processes the logic, and

 

 

 

 

 

writes outputs; communication and hardware/software tests are

 

 

 

 

 

carried out.

 

 

 

 

 

 

 

 

Green

 

Flash

The CPU is in STOP and is not executing any user program. All outputs

 

 

 

 

 

are reset to a safe de-energized state. STOP can be triggered by

 

 

 

 

 

setting the Emergency stop system variable to TRUE in the user

 

 

 

 

 

program or by a direct command from the PC. Seen when PLC is

 

 

 

 

 

switched on for approximately 10s during the system check.

 

 

 

 

 

 

 

Not illuminated

Off

The CPU in ERROR STOP (see ERROR below).

 

 

 

 

 

ERROR

Red

 

On

The CPU has discovered a hardware fault in the CPU and is switching

 

 

 

 

 

to ERROR STOP. The CPU has discovered a software error in the

 

 

 

 

 

operating system. The watchdog has triggered ERROR STOP,

 

 

 

 

 

because the cycle time has been exceeded. The CPU has stopped the

 

 

 

 

 

execution of the user program, ended all hardware and software tests,

 

 

 

 

 

and all outputs have been reset. The CPU can only be started again

 

 

 

 

 

through a command from the PC.

 

 

 

 

 

 

 

Not illuminated

Off

No error has been detected.

 

 

 

 

PROG

Orange

On

The CPU is being loaded with a new configuration.

 

 

 

 

 

 

 

Orange

Flash

The Flash ROM is being loaded with a new operating system.

 

 

 

 

 

 

 

Not illuminated

Off

No loading of configuration or operating system.

 

 

 

 

FORCE

Not illuminated

Off

FORCE is not signalled.

 

 

 

 

 

 

 

Orange

On

Forcing active.

 

 

 

 

FAULT

Orange

On

Error display for Line Control. The user program has caused an error.

 

 

 

 

 

The PES configuration is faulty. The loading of a new operating system

 

 

 

 

 

was faulty, and the operating system is corrupt.

 

 

 

 

 

 

 

Orange

Flash

An error has occured during the write cycle for a Flash ROM (during

 

 

 

 

 

the oprating system update). One or more I/O errors have occured.

 

 

 

 

 

 

 

Not illuminated

Off

None of the above errors has occured.

 

 

 

 

OSL

Orange

Flash

Emergency loader of the operating system is active.

 

 

 

 

BL

Orange

Flash

COM in INIT_FAIL state.

 

 

 

 

 

 

33003405 07/2007

45

Page 45
Image 45
Schneider Electric XPSMF2DO801 LED Description, Following table describes behaviors of the LEDs, Color Status Meaning