Equipment Description

Operation

Up to COM OS version 8.32 all Ethernet ports of the integrated Ethernet switches

Parameters of

have the same settings:

 

the Ethernet

￿

Autoneg/Autoneg for Speed Mode

 

Interfaces

￿

Flow-control Mode

 

 

Other settings are not possible and will be rejected by the PLC when loading a

 

configuration.

 

 

The Ethernet interfaces 10/100 BaseT of the device have the following parameters:

 

 

 

 

Firm operating parameters

 

 

 

 

 

Speed Mode

Autoneg

 

 

 

 

Flow-Control Mode

Autoneg

 

 

 

 

Other devices combined with the Safety PLC or remote I/O device must have the following network settings:

Admissible settings of other devices

Speed Mode

Autoneg

 

 

Flow-Control Mode

Autoneg

 

 

or

 

 

 

Speed Mode

Autoneg

 

 

Flow-Control Mode

Half Duplex

 

 

or

 

 

 

Speed Mode

10 or 100 Mbit/s

 

 

Flow-Control Mode

Half Duplex

 

 

 

 

Non-admissible settings of other devices

 

 

 

Speed Mode

Autoneg or 10 or 100 Mbit/s

 

 

Flow-Control Mode

Full Duplex

 

 

For COM OS version > 8.32 and XPSMFWIN Hardware Management version

>7.56.10 each Ethernet port of the integrated switch can be individually configured. See also in the appendix Connection Diagrams, Examples of Application, and Error Codes, p. 67.