Brief description of the functional devices

 

The following table contains the parameter descriptions:

 

 

 

 

Parameter

Description

 

 

 

 

Port

Port number, as assigned on device.

 

 

Note: Only 1 configuration is possible per port.

 

 

Value range 1...n, depending on the resource

 

 

 

 

Speed [MBit/s]

The following selections are available:

 

 

10 MBit/s data rate 10 MBit/s

 

 

100 MBit/s data rate 100 MBit/s

 

 

Autoneg (10/100) automatic setting of the baud rate

 

 

The default setting is Autoneg.

 

 

 

 

Flow control

The following selections are available:

 

 

Full duplex communication in both directions at the same time

 

 

Half duplex communication in one direction

 

 

Autoneg automatic control of communication

 

 

The default setting is Autoneg.

 

 

 

 

Autoneg also with

The Advertising (transfer of Speed and Flow control properties) is

 

fix values

made with fixed parameter values. Thereby other devices, whose port

 

 

settings are Autoneg, can recognise how the PLC ports are set.

 

 

 

 

Limit

Limit incoming Multicast and/or Broadcast packages.

 

 

The following selections are available:

 

 

Off no limit

 

 

Broadcast limit Broadcast (128 kbit/s)

 

 

Multicast and Broadcast limit Multicast and Broadcast (1024 kbit/s)

 

 

The default setting is Broadcast.

 

 

 

 

 

 

 

 

 

 

 

 

Activation of Parameters are set in the COM window of the Hardware Management screen.

Settings Before the changes/settings become active the application program must be compiled using the Code Generator and then transferred to the PLC(s). The communication properties can be changed in the online mode using the Control Panel. The settings become active immediately, but are not transferred to the application program.