Application and Function

Short-Circuit

Characteristics

of the Output

Channels

If a short-circuit occurs in an output channel, the safety remote device switches off the affected channel. If multiple short-circuits occur, the channels are switched off individually in accordance with their power consumption.

If the maximally permitted current for all outputs is exceeded, all outputs are shut down and cyclically reconnected.

 

 

 

WARNING

 

 

 

 

 

 

 

 

 

 

 

SHORT-CIRCUIT CONDITION

 

 

The output circuit terminals must not be connected with the connected load. In case

 

 

of a short-circuit, the resulting high current may damage the terminals.

 

 

Failure to follow these instructions can result in death, serious injury, or

 

 

equipment damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Diagnostics

Using the XPSMFWIN programming environment, all the safety remote output

 

 

device’s diagnostics can be viewed. Each safety remote device provides diagnostic

 

 

signals with reference to their status, error codes, and channel status.

 

 

In XPSMFWIN all diagnostic information can be viewed in two ways:

 

 

￿ Using the On-linetest function - it can monitor the values of the signals and

 

 

variables within the logic plan, while the systems are executing the program.

 

 

￿ Using the Diagnostics window that displays all states of the CPU, COM, and

 

 

I/O modules.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 