Ports and Displays

!Warning

Industrial Ethernet ELS TP40 switches are designed for operation with safety extra-low voltage. This means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/ VDE0805 can be connected to the power supply terminals.

The power supply unit to supply the ELS TP40 must comply with NEC Class 2 (voltage range 18 - 32 V, current requirement 150 mA).

Never connect the ELS to a.c. power supplies or d.c. power supplies greater than 32 V d.c.

Power Supply

The power supply is connected over a high resistance with the enclosure to allow an ungrounded setup. The ELS TP40 device can also be grounded using the PE screw terminal on the terminal block.

Industrial Ethernet

25

A5E00152007-03

Page 25
Image 25
Siemens Electrical Lean Switch installation instructions Power Supply