Diagnostics over Industrial Ethernet

Construction of the Trap report

The ELS knows 2 kinds of traps:

Coldstart

Change of port status

In case of Power On a Coldstart-trapwill be sent.

If the link-status of a port changes the current contents of the LED-STATUS Re- gister will be sent.

LED-Status:

Byte 3

Byte 2

Byte 1

Byte 0

Port 4

Port 3

Port 2

Port 1

Port Status:

Bit 7

Bit 6

 

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

0

 

0

Link

0

0

Duplex

Speed

 

Link

1

= Link is up

 

 

 

 

 

 

 

0

= Link is down

 

 

 

 

 

Duplex

1

= Link is full duplex

 

 

 

 

 

 

0

= Link is half duplex

 

 

 

 

 

Speed

1

= Speed is 100Mbps

 

 

 

 

 

 

0

= Speed is

10Mbps

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

Port 1:

Link Up , full duplex, 100 MB

 

 

 

 

Port 2:

Link down

 

 

 

 

 

 

Port 3:

Link down

 

 

 

 

 

 

Port 4:

Link Up , half duplex, 10 MB

 

 

 

Inhalt in LED-Status

10000013hex // 268435475 dez

Note

Leading Zeros might not be shown by your management system.

68

Industrial Ethernet

A5E00152007-03

Page 68
Image 68
Siemens Electrical Lean Switch installation instructions Construction of the Trap report, LED-Status, Port Status