Siemens G85139 operating instructions Front Panel Controls & Basic Operation

Models: G85139

1 42
Download 42 pages 12.94 Kb
Page 14
Image 14

English

3. FRONT PANEL CONTROLS & BASIC OPERATION

3. FRONT PANEL CONTROLS & BASIC OPERATION

3.1 Front Panel Controls

CAUTION

The digital frequency setpoint has been set at 5.00 Hz in the factory. This means that, it is not necessary to enter a frequency setpoint via the Δ button or parameter P005 in order to test that the motor turns following a RUN command.

All settings must only be entered by qualified personnel, paying particular attention to the safety precautions and warnings.

The parameter settings required can be entered using the three parameterisation buttons (P, Δ and ) on the front panel of the inverter. The parameter numbers and values are indicated on the four digit LED display.

 

LED Display

JOG

FORWARD / REVERSE

Button

Button

 

RUN

UP / INCREASE

Button

Frequency

 

Jog

STOP

DOWN / DECREASE

Button

Frequency

 

RS485

P

 

Interface

 

 

Parameterisation

Removable

Button

 

Cover Strip

 

Jog

LED Display

P

Pressing this button while the inverter is stopped causes it to start and run at the preset jog frequency. The inverter stops as soon as the button is released. Pressing this button while the inverter is running has no effect. Disabled if P123 = 0.

Press to start the inverter. Disabled if P121 = 0.

Press to stop the inverter.

Displays frequency (default), parameter numbers or parameter values (when P is pressed) or fault codes.

Press to change the direction of rotation of the motor. REVERSE is indicated by a minus sign (values < 100) or a flashing decimal point (values > 100). Disabled if P122 = 0

Press to INCREASE frequency. Used to change parameter numbers or values to higher settings during the parameterisation procedure. Disabled if P124 = 0.

Press to DECREASE frequency. Used to change parameter numbers or values to lower settings during the parameterisation procedure. Disabled if P124 = 0.

Press to access parameters. Disabled if P051 - P053 = 14 when using digital inputs.

Figure 9: Front Panel

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

14

 

Page 14
Image 14
Siemens G85139 operating instructions Front Panel Controls & Basic Operation