5. SYSTEM PARAMETERS

Parameter

 

Function

 

Range

 

Description / Notes

 

 

 

 

[Default]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P092 Serial link baud rate

3 - 7

 

[6]

P093 Serial link timeout (seconds)

0 - 240

 

[0]

P094

 

Serial link nominal system setpoint

0 - 400.00

 

 

 

(Hz)

[50.00]

 

 

 

 

 

 

P095

 

USS compatibility

0 - 2

 

 

 

 

[0]

 

 

 

 

 

 

P099

 

Option module type

0 - 1

 

 

 

 

 

[0]

P101

 

Operation for Europe or USA

0 - 1

 

 

 

 

[0]

P111

 

Inverter power rating (kW/hp)

0.0 - 50.00

 

 

 

[

]

 

 

 

 

 

 

P112

 

Inverter type (model)

[

1 - 7

 

 

 

]

P113

Inverter type (power rating)

0 - 29

 

[

]

Sets the baud rate of the RS485 serial interface (USS protocol):

3= 1200 baud

4= 2400 baud

5= 4800 baud

6= 9600 baud

7= 19200 baud

Note: Some RS232 to RS485 converters are not capable of baud rates higher than 4800.

This is the maximum permissible period between two incoming data telegrams. This feature is used to turn off the inverter in the event of a communications failure.

Timing starts after a valid data telegram has been received and if a further data telegram is not received within the specified time period, the inverter will trip and display fault code F008.

Setting the value to zero switches off the control.

Setpoints are transmitted to the inverter via the serial link as percentages. The value entered in this parameter represents 100% (HSW = 4000H).

0 = Compatible with 0.1 Hz resolution

1 = Enable 0.01 Hz resolution

2 = HSW is not scaled but represents the actual frequency value to a resolution of 0.01 Hz (e.g. 5000 = 50 Hz).

0 = Option module not present

1 = PROFIBUS module (enables parameters relating to PROFIBUS)

This sets the inverter for European or USA supply and motor frequency:

0 = Europe (50 Hz)

1 = USA (60 Hz)

Note: After setting P101 = 1 the inverter must be re-set to factory defaults. i.e. P944 = 1 to automatically set P013 = 60 Hz, P081 = 60 Hz, P082 = 1680 rpm and P085 will be displayed in hp.

Read-only parameter that indicates the power rating of the inverter in kW. e.g. 0.55 = 550 W

Note: If P101 = 1 then the rating is displayed in hp.

Read-only parameter.

 

 

 

 

 

1 = MICROMASTER series 2 (MM2)

 

 

 

2 =

COMBIMASTER

 

 

 

 

 

3 =

MIDIMASTER

 

 

 

 

 

4 = MICROMASTER Junior (MMJ)

 

 

 

5 = MICROMASTER series 3 (MM3)

 

 

 

6 = MICROMASTER Vector (MMV)

 

 

 

7 = MIDIMASTER Vector (MDV)

 

 

 

 

 

 

 

 

 

 

Read-only parameter.

 

 

 

 

 

0 =

MM12

10

= MM12/2

20

= MM37/3

1 =

MM25

11

= MM25/2

21

= MM55/3

2 =

MM37

12

= MM37/2

22

= MM75/3

3 =

MM55

13

= MM55/2

23

= MM110/3

4 =

MM75

14

= MM75/2

24

= MM150/3

5 =

MM110

15

= MM110/2

25

= MM220/3

6 =

MM150

16

= MM150/2

26

= MM300/3

7 =

MM220

17

= MM220/2

27

= MM400/3

8 =

MM300

18

= MM300/2

28

= MM550/3

 

 

 

19

= MM400/2

29

= MM750/3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G85139-H1750-U049-B