Setup procedure for a simple application

Motor:

220 V

 

1.5 kW output power

Application requirements:

Setpoint adjustable via potentiometer 0 - 50 Hz

 

Ramp up from 0 to 50 Hz in 15 seconds

 

Ramp down from 50 to 0 Hz in 20 seconds

Inverter used:

MM150 (6SE9216-8BB40)

Settings:

P009 = 2 (all parameters can be altered)

 

P081

- P085 = values given on motor rating plate

 

P006

= 1 (analogue input)

 

P002

= 15 (ramp up time)

 

P003

= 20 (ramp down time)

This application is now to be modified as follows:

Operation of motor up to 75 Hz

i.e.

V

 

 

(voltage/frequency curve is linear up to 50 Hz).

 

 

 

220

 

 

Motor potentiometer setpoint in addition to

 

 

 

analogue setpoint .

 

 

 

 

Use of analogue setpoint at maximum 10 Hz.

 

 

 

 

Ramp times to remain the same.

 

50

75

 

 

 

f (Hz)

 

 

 

 

Parameter adjustments:

P009 = 2

(all parameters can be altered)

 

P013

= 75

(maximum motor frequency in Hz)

 

P006

= 2

(setpoint via motor potentiometer or fixed setpoint)

 

P024

= 1

(analogue setpoint is added)

 

P022

= 10

(maximum analogue setpoint at 10 V = 10 Hz)

8.2 USS Status Codes

The following list gives the meaning of status codes displayed on the front panel of the inverter when the serial link is in use and parameter P001 is set to 006:

001Message OK

002Slave address received

100Invalid start character

101Timeout

102Checksum error

103Incorrect message length

104Parity fail

Notes

(1)The display flashes whenever a byte is received, thus giving a basic indication that a serial link connection is established.

(2)If ‘100’ flashes on the display continuously, this usually indicates a bus termination fault.