Siemens G85139 operating instructions P051, P052, P053, P056

Models: G85139

1 42
Download 42 pages 12.94 Kb
Page 26
Image 26

English

Parameter

Function

Range

 

 

[Default]

 

 

 

 

 

P051

Selection control function, DIN1

0 - 19

 

(terminal 5), fixed frequency 3

[1]

 

or binary fixed frequency bit 0.

 

P052

Selection control function, DIN2

0 - 19

 

(terminal 6), fixed frequency 2.

[2]

 

or binary fixed frequency bit 1.

 

P053

Selection control function, DIN3

0 - 19

 

(terminal 7), fixed frequency 1

 

 

or binary fixed frequency bit 2.

[6]

5. SYSTEM PARAMETERS

Description / Notes

Value

 

Function of P051 to P053

 

Function,

Function,

 

 

 

 

low state

high state

0

 

Input disabled

-

-

1

 

ON right

 

Off

On right

2

 

ON left

 

Off

On left

3

 

Reverse

 

Normal

Reverse

4

 

OFF2 **

 

OFF2

On

5

 

OFF3 **

 

OFF3

On

6

 

Fixed frequencies 1 - 3

 

Off

On

7

 

Jog right

 

Off

Jog right

8

 

Jog left

 

Off

Jog left

9

 

Remote operation

 

Local

Remote

10

 

Fault code reset

 

Off

Reset on

11

 

 

 

 

rising edge

 

Increase frequency *

 

Off

Increase

12

 

Decrease frequency *

 

Off

Decrease

13

 

Disable analogue input

 

Analogue on

Analogue

14

 

(setpoint is 0.0 Hz)

 

 

disabled

 

Disable the ability to change

 

enabled

disabled

15

 

parameters

 

 

 

 

Enable dc brake

 

Off

Brake on

16

 

Do not use

-

-

17

 

Binary fixed frequency control

 

Off

On

18

 

(fixed frequencies 1 - 7)

 

 

 

 

As 6, but input high will also

 

Off

On

19

 

request RUN *

 

 

 

 

External trip/PTC

 

Yes (F012)

No

 

 

 

 

 

 

P056

 

Digital input debounce time

0 - 2

 

 

 

[0]

 

 

 

 

 

*Only effective when P007 = 0.

**See section 4.3.

Binary Coded Fixed Frequency Mapping

(P051, P052, P053 = 17)

 

 

 

 

DIN3

DIN2

DIN1

 

 

 

 

 

(P053)

(P052)

(P051)

 

 

 

STOP

0

 

 

 

 

 

0

0

 

 

 

RUN to FF1 (P041)

0

 

 

 

 

 

0

1

 

 

 

RUN to FF2 (P042)

0

 

 

 

 

 

1

0

 

 

 

RUN to FF3 (P043)

0

 

 

 

 

 

1

1

 

 

 

RUN to FF4 (P044)

1

 

 

 

 

 

0

0

 

 

 

RUN to FF5 (P046)

1

 

 

 

 

 

0

1

 

 

 

RUN to FF6 (P047)

1

 

 

 

 

 

1

0

 

 

 

RUN to FF7 (P048)

1

 

 

 

 

 

1

1

 

 

 

 

 

 

 

 

 

0 =

12.5 ms

 

 

 

 

1 =

7.5 ms

 

 

 

 

2 =

2.5 ms

 

 

 

 

 

 

 

 

 

 

 

 

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

26

 