Electrical Requirements
75 Pound Gas and Steam Models
NOTE: Wire size and breaker ratings were obtained from the Canadian Electrical Code for 75 C. wire and are intended for use as a guideline only. Electrical connections should be made by a qualified electrical contractor in accordance with all applicable local and national requirements.
NOTE: Electrical specifications below are subject to change without notice. Always refer to product serial plate for most current specifications of product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.NOTE: 3 Phase Only – Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).
|
| Terminal Block | Serial Plate Amps | Recommended Circuit | ||||
|
|
|
|
|
|
| ||
Serial Plate Rating |
| Connections | Nonreversing | Reversing | Breaker | Wire Size | ||
|
| Required | Rating | AWG (mm2) | ||||
120V/60Hz/1ph |
| L1, Neutral and ground | 13.8 |
| N/A | 20A – 1 pole | 12 (3.31) | |
|
|
|
|
|
|
|
|
|
| L1, Neutral and ground | 7.6 |
| N/A | 15A – 1 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
|
|
| L1, L2 and ground | 7.6 |
| N/A | 15A – 2 pole | 14 (2.08) | ||
1ph |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| L1, Neutral and ground | 6.7 |
| 7.0 | 15A – 1 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
|
|
| L1, L2, L3 and ground | 3.8 |
| 4.3 | 10A – 3 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
|
|
200V/50Hz/3ph |
| L1, L2, L3 and ground | 3.5 |
| 4.5 | 10A – 3 pole | 14 (2.08) | |
|
|
|
|
|
|
|
|
|
240V/60Hz/3ph |
| L1, L2, L3 and ground | 3.8 |
| 4.3 | 10A – 3 pole | 14 (2.08) | |
|
|
|
|
|
|
|
|
|
| L1, L2, L3 and ground | 3.5 |
| 4.9 | 10A – 3 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
|
|
380V/50 or 60Hz/3ph |
| L1, L2, L3 and ground | 1.8 |
| 2.1 | 10A – 3 pole | 14 (2.08) | |
|
|
|
|
|
|
|
|
|
| L1, L2, L3 and ground | 1.8 |
| 2.1 | 10A – 3 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
|
|
440V/60Hz/3ph |
| L1, L2, L3 and ground | 1.9 |
| 2.1 | 10A – 3 pole | 14 (2.08) | |
|
|
|
|
|
|
|
|
|
| L1, L2, L3 and ground | 1.9 |
| 2.1 | 10A – 3 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
|
|
N/A = Not Applicable |
|
|
|
|
|
|
|
|
|
|
|
| Table 8 |
|
|
| |
F75 Gas Models Only |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Terminal Block |
| Serial Plate Amps | Recommended Circuit | |||
|
|
|
|
|
|
|
| |
Serial Plate Rating |
| Connections |
| Nonreversing |
| Reversing | Breaker | Wire Size |
|
| Required |
|
| Rating | AWG (mm2) | ||
L1, L2, L3 and ground |
| N/A |
| 6.3 | 15A – 3 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
| |
240V/60Hz/3ph | L1, L2, L3 and ground |
| N/A |
| 6.3 | 15A – 3 pole | 14 (2.08) | |
|
|
|
|
|
|
|
| |
L1, L2, L3 and ground |
| N/A |
| 3.1 | 10A – 3 pole | 14 (2.08) | ||
|
|
|
|
|
|
|
|
|
N/A = Not Applicable |
|
|
|
|
|
|
|
|
Table 9
M414905 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | 45 |