Electrical Requirements
50 and 75 Pound Electric Models
Refer to Table 10.
NOTE: Wire size and breaker ratings were obtained from the Canadian Electrical Code for 75 C. wire and are intended for use as a guideline only. Electrical connections should be made by a qualified electrical contractor in accordance with all applicable local and national requirements.
NOTE: Electrical specifications below are subject to change without notice. Always refer to product serial plate for most current specifications of product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).
| Terminal Block | Serial Plate Amps | Recommended Circuit | ||
|
|
|
|
| |
Serial Plate Rating | Connections | Nonreversing | Reversing | Breaker | Wire Size |
| Required | Rating | AWG (mm2) | ||
240V/50Hz/1ph | L1, Neutral and Ground | 93 | 95 | 125A – 1 pole | 1 (42.4) |
(50 Pound only) |
|
|
|
|
|
|
|
|
|
|
|
L1, L2, L3 and ground | 89 | 88 | 125A – 3 pole | 1 (42.4) | |
|
|
|
|
|
|
200V/50Hz/3ph | L1, L2, L3 and ground | 84 | 85 | 125A – 3 pole | 1 (42.4) |
|
|
|
|
|
|
230V/50Hz/3ph | L1, L2, L3 and ground | 73 | 75 | 100A – 3 pole | 3 (26.7) |
|
|
|
|
|
|
240V/50Hz/3ph | L1, L2, L3 and ground | 79 | 78 | 100A – 3 pole | 3 (26.7) |
|
|
|
|
|
|
240V/60Hz/3ph | L1, L2, L3 and ground | 79 | 78 | 100A – 3 pole | 3 (26.7) |
|
|
|
|
|
|
380V/50 or 60Hz/3ph | L1, L2, L3 and ground | 47 | 48 | 60A – 3 pole | 6 (13.3) |
|
|
|
|
|
|
L1, L2, L3 and ground | 43 | 44 | 60A – 3 pole | 6 (13.3) | |
|
|
|
|
|
|
440V/60Hz/3ph | L1, L2, L3 and ground | 41 | 41 | 51A – 3 pole | 6 (13.3) |
|
|
|
|
|
|
480V/60Hz/3ph | L1, L2, L3 and ground | 38 | 38 | 50A – 3 pole | 6 (13.3) |
|
|
|
|
|
|
Table 10