SPX Cooling Technologies TG MAG185-125 3.18.7.1Transport of pump unit, T-jacketon pump cover

Models: TG MAG86-100 TG MAG23-65 TG MAG58-80 TG MAG15-50 TG MAG185-125

1 72
Download 72 pages 42.17 Kb
Page 35
Image 35
T-jacket on pump cover

T-jacket on pump cover

dk dk

2xCf

dh

dg

ma

zk

zh

2xCf

 

 

 

zm

Bh

Bg

 

3. Jacket on pump cover

In case of steam supply, connect the supply line at the highest position and the return line

to the lowest position so that condensed water will be drained via the lowest line. In case of liquid supply, the positions are not important. A drain plug Bh is provided and can be considered as a drain line.

4.Jackets on safety relief valve – around spring casing The jackets on the safety relief valve are designed for

use with saturated steam (max 10 bar, 180°C) or with non-dangerous media. They are provided with threaded connections Bo (see chapter 6.0 for dimensions).

The connection can be done by threaded pipes or pipe connections with sealing in the thread (conical thread applying ISO 7/1). Thread type see section 3.21.7.

3. Jacket on pump cover Bo

Bo

3.18.7 Guidelines for assembly

When a bare shaft pump is delivered, the assembly with drive is the responsibility of the user. The user also must provide all necessary devices and equipment allowing a safe installation and commissioning of the pump.

3.18.7.1Transport of pump unit

Prior to lifting and transporting a pump unit, make sure that the packaging is of sturdy enough construction and will not be damaged during transport.

Use crane hooks in the baseplate or the frame. (See chapter 1.0.)

3.18.7.2Foundation pump unit

The pump unit must be installed on a base plate or on a frame placed exactly level on the foundation. The foundation must be hard, level, flat and vibration free in order to guarantee the alignment of pump/drive while operating. (See section 3.18.2.5)

3.18.7.3Variators, Gear box, Gear motors, Motors

Consult the suppliers’s instruction manual , included with the delivery. Contact the pump supplier if the manual is not included.

3.18.7.4Electric motor drive

Before connecting an electric motor to the mains check the prevailing local regulations of your electricity provider as well as the EN 60204-1 standard.

Leave the connecting of electric motors to qualified personnel. Take the necessary measures to prevent damage to electrical connections and wiring.

A.0500.551 – IM-TGMAG/02.00 EN (02/2008)

35

Page 35
Image 35
SPX Cooling Technologies TG MAG185-125 3.18.7.1Transport of pump unit, 3.18.7.2Foundation pump unit, T-jacketon pump cover