Circuit breaker
For safety work on a pump unit, install a circuit breaker as close as possible to the machine. It also is advisable to place an earth fault circuit breaker. The switching equipment must comply with prevailing regulations, as stipulated by EN
Motor overload protection
To protect the motor against overloads and
Connection
•Do not use a
•For
•Ensure a sufficiently high starting torque for
Electrical equipment, terminals and com- ponents of control systems may still carry live current when at rest. Contact with these may be fatal, result in serious injury or
L1
L2
U
L1
L2
U
cause irreparable material damage.
Line | Motor |
| |
U (volt) | 230/400 V |
| 400 V |
3 x 230 V | delta |
| – |
3 x 400 V | star |
| delta |
|
|
|
|
L3
N
L3
N
3.18.7.5 Combustion engines
When using a combustion engine in the pump unit, see the engine instruction manual included in the delivery. Contact the pump supplier if the manual is not included.
Irrespective of this manual the following must be respected for all combustion engines:
delta
U1
V1 W1
W2 U2 V2
star
U1 V1 W1
W2 U2 V2
•Compliance with local safety regulations
•The exhaust of combustion gases must be screened to avoid contact
•The starter must be uncoupled automatically once the engine has started
•The
•Before starting the engine, the oil level must be checked
Note!
•Never run the engine in a closed area
•Never refuel the engine while it is still running
3.18.7.6Shaft coupling
Internal gear pumps demand a relatively high starting torque. During the operation shock loads occur due to pulsations inherent to the gear pump principle. Therefore, choose a coupling which
is 1.5 times the torque recommended for normal constant load.
Fit – without impact tool – both halves of the coupling to the pump shaft and the motor shaft respectively.
Alignment
The pump and motor shafts of complete units are accurately
Alignment of the coupling halves may only take place by moving the electric motor!
36 | A.0500.551 – |