3.18.2.1Short suction line

3.18.2 Location

3.18.2.1Short suction line

Locate the pump/pump unit as close as possible to the liquid source and if possible below the liquid supply level. The better the suction conditions, the better the performance of the pump. See also section 3.18.5.2 Piping.

3.18.2.2Accessibility

Sufficient space should be left around the pump/pump unit to allow proper inspection, pump isolation and maintenance.

Sufficient space should be left in front of the pump to enable disassembly of the pump cover, idler and idler pin.

For loosening pump cover refer to ma

For disassembling rotating parts (rotor shaft and magnetic coupling) refer to mb

To adjust pressure of safety relief valve refer to mc

For dimensions of ma, mb, mc see chapter 6.0.

mamb

mc3.18.2.2Accessibilitymamb

mc

It is imperative that the operating device of pump and/or pump unit is always accessible (also during operation).

3.18.2.3Outdoor installation

The TopGear pump may be installed in the open, the ball bearings are sealed by rubber V-joints protecting the pump against dripping water. In very wet conditions we advice to install a roof.

3.18.2.4Indoor installation

Locate the pump so that the motor can be vented properly. Prepare the motor for operation according to instructions provided by the motor manufacturer.

When flammable or explosive products are pumped, a proper earthing should be provided. The components of the unit should be connected with earthing bridges to reduce the danger arising from static electricity.

Use explosion free or explosion proof motors according to local regulations. Provide suitable coupling guards and suitable couplings.

Excessive temperatures

Depending on the fluid being pumped, high temperatures may be reached inside and around the pump. From 60°C onwards the safety representative must provide the necessary protective means and place “Hot surfaces” notices.

When insulating the pump unit, ensure that adequate cooling is allowed for the bearing housing. This is required for cooling of the bearings and grease of the bearing bracket.

(see 3.18.7.7 Guarding of moving parts).

Protect the user against leakages and possible liquid streams.