4.2.4Disassembly of pump shaft complete
1.Remove key (1570) from the pump shaft.
2.Remove sealing segment (1490) from the bearing bracket (see picture).
1570 | 8640 |
Piercer1490
Screw driver | 0702 |
|
1540
8320
3.Remove circlip (8640) from the rear end of the shaft.
4.
Remark: The pump shaft (0702) can be rotated to allow access to these screws. Be care- ful that the spanner does not damage the magnets in the outer magnectic rotor (8320).
5.Drive out the complete pump shaft to the front by tapping with a plastic hammer on the pump shaft (0702).
4.2.5Disassembly of outer magnetic rotor
1.
2.Use threaded holes in the flange of the pump shaft to remove the outer magnetic rotor (8320).
Removal of ball bearings
1.Remove circlips (1450) and support ring (1460) from the pump shaft (0702).
2.Remove the bearing (1440) from
the shaft using a
3.Remove the bearing cover (1430) from the pump shaft (0702).
4.Remove both circlips (8620) from
the bearing bracket (1400) to the front.
5.Drive out ball bearing (1440)
from the bearing bracket (1400) to the rear.
8320
8610
0702
1430
1440
1460
1450
8620
8620
1400
1440
A.0500.551 – | 51 |