Alarms

Several alarm options are available for the Digital Dosing feeder. The standard unit comes with

a flashing alarm symbol on the faceplate. Options include both audible horns and flashing lights. An optional no voltage alarm relay can be connected to the user’s central alarm system.

Level Probes

To adjust the level probes:

1.Turn the controller ON.

2.Fill the dosing station until the level sensor is one-third covered.

3.Remove the small plastic screw (M3) on the back of the level sensor (see Figure 7).

LED Yellow (Station)

LED Green (Level Probe)

 

 

 

 

 

 

on: Station Filled

on: Power Supply Available

 

 

 

 

 

 

off: Station Emptied

off: Power Supply Not Available

 

 

 

 

 

 

 

npn: Normally Closed

 

 

 

 

 

npn: Normally Open

 

pnp: Normally Open 1

 

 

 

 

0 pnp: Normally Closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blind Lid

Trim-pot with

Protective Screw

Plastic Screw M3

Cable

 

Level Probe

Figure 7. Level Sensor Screw

4. Turn the trim-pot until the yellow control lamp just switches off.

NOTE: Turning the trim-pot to the left decreases the switching sensitivity; turning it to the right increases the switching sensitivity.

5.Fill the dosing station until the level probe is two-thirds covered. The yellow control lamp should now switch on again. If not, repeat Step 4.

6.Reinstall the plastic screw (M3).

NOTE: The sliding switch under the cover must be set on “0”.