Rack-mountable Tray
3-52 Sixth Edition 95741
Power-On Rack
1. Make sure the rack fan power cord is connected to the single outlet of the rack PDU
power strip.
2. Attach the female end of the rack power cord to the connector on the left side of the rack
PDU power strip (see figure).
Note: When the RACK001 has more than four trays installed, a second PDU power strip
must be obtained and installed approximately 9 inches above the existing power
strip (see “Install Optional Second Power Strip” on page 3-29).
The second PDU power strip, if installed, must be powered by a separate power
cord and source.
3. Route the power cord/s through the floor of the rack, and attach the male end of the
power cord to a power source.
Note: To comply with safety agency standards, the socket/s shall be installed near the
equipment and shall be easily accessible.
1. Fan power cord
2. PDU power switch
3. Input power cord to rack PDU
4. Place the PDU power switch/es to the ON position.
5. Press the power switch on each installed tray to the ON position.
6. Verify that all installed trays are operational.
Note: A steady asterisk on the operator panel indicates a successful IPL completion, the
drive is online, but not loaded with a cartridge.
7. Proceed to “Configure the Drive” on page 3-53.