95741 Sixth Edition 3-45
Rack-mountable Tray
Attach Tray Power Cord
Use the instructions below to attach the power cord between a drive or CSL tray
and the rack power distribution unit (PDU) power strip:
1. Attach the female end of the power cord, part number 10083590, to the AC receptacle on
the tray.
Note: The figure shows the location of the receptacle on a CSL tray. The receptacle on a
drive tray is in a different location.
If you are not using StorageTek RACK001, a different power cord may be required
for the tray.
2. Attach the male end of the power cord to one of the 4-ganged outlets on the rack PDU
power strip.
Note: Earlier deliveries of StorageTek RACK001 may contain a PDU power strip which
has a 6-ganged outlet group.
3. Repeat Step 1 and Step 2 for all remaining CSL or drive trays.
Note: The RACK001 PDU power strip has a maximum of 12 Amps across the ganged
outlets available for powering trays.
The additional, single outlet is reserved for the rack fan power cord.
When installing more than four trays, a second PDU power strip must be obtained
and installed approximately 9 inches above the existing power strip (see “Install
Optional Second Power Strip” on page 3-29).
If you have the earlier, 6-ganged outlet PDU power strip, you should limit it to
powering a maximum of four trays, and obtain a second PDU power strip for
additional trays (see “Install Optional Second Power Strip” on page 3-29).
4. Slide the power cables into the brackets along the side of the frame.
1. Tray power cord
2. Fan power cord
1
2