TABLE 2-2 Cluster Platform Rack Components
| Component | Quantity | 
| 
 | 
 | 
| Sun StorEdge expansion cabinet | 1 | 
| Ethernet hub | 1 | 
| Netra T1 AC200 management server | 1 | 
| Netra st D130 boot disks | 4 | 
| Air baffle | 2 | 
| Sun Enterprise cluster node | 2 | 
| Sun StorEdge T3 array | 2 | 
| Terminal concentrator | 1 | 
| 
 | 
 | 
Power and Heating Requirements
The Cluster Platform 4500/3 hardware should have two dedicated AC breaker panels. The cabinet should not share these breaker panels with other, unrelated equipment. The system requires two 
If the cabinet is installed on a raised floor, cool conditioned air should be directed to the bottom of each rack through perforated panels.
The 
TABLE 2-3 Power and Heat Requirements for Cluster Platforms
| Maximum Power Draw | Heat Dissipation | |
| 
 | 
 | 
 | 
| 1 | 10480 W | 33786 BTUs/hr. | 
| 
 | 
 | 
 | 