TABLE 2-2Cluster Platform Rack Components

Component

Quantity

 

 

Sun StorEdge expansion cabinet

1

Ethernet hub

1

Netra T1 AC200 management server

1

Netra st D130 boot disks

4

Air baffle

2

Sun Enterprise cluster node

2

Sun StorEdge T3 array

2

Terminal concentrator

1

 

 

Power and Heating Requirements

The Cluster Platform 4500/3 hardware should have two dedicated AC breaker panels. The cabinet should not share these breaker panels with other, unrelated equipment. The system requires two L30-R receptacles for the cabinet, split between two isolated circuits. For international installations, the system requires two Blue 32AIEC309 (international) receptacles.

If the cabinet is installed on a raised floor, cool conditioned air should be directed to the bottom of each rack through perforated panels.

The 72-inch cabinet in the Cluster Platform 4500/3 consumes power and dissipates heat, as shown in TABLE 2-3.

TABLE 2-3Power and Heat Requirements for Cluster Platforms

72-Inch Cabinet

Maximum Power Draw

Heat Dissipation

 

 

 

1

10480 W

33786 BTUs/hr.

 

 

 

Chapter 2 The Cluster Platform 4500/3 System 15

Page 27
Image 27
Sun Microsystems 4500/3 manual Power and Heating Requirements, 2Cluster Platform Rack Components