12 - 53
12. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions:
M
Servo
amplifier
MR-J2S-60B
Servo motor
HC-MFS73
Ig1 Ig2
Iga Igm
NV
2mm2 5m 2mm2 5m
Use a leakage current breaker designed for suppressing harmonics/surges.
Find the terms of Equation (12.2) from the diagram:
Ig1 20 1000
50.1 [mA]
Ig2 20 1000
50.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (12.2):
Ig 10 {0.1 00.1 3(0.1 0.1)}
4 [mA]
According to the result of calculation, use a leakage current breaker having the rated sen sitivity
current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/SW/CW/HW series.