E658130

5.2.Communication parameters for CCL003Z

Title

Function

Description

c100

Communication error detection

0.0 - 100.0 sec.

delay time

 

 

c101

 

0: Stop and controlled by cmod, fmod

 

 

1: Operation continue

 

Inverter operation at the

2: Deceleration stop

 

communication loss action

3: Coast stop

 

 

4: Network error stop (err8 trip)

 

 

5: Preset speed operation (by c102 setting)

c102

Preset speed

0: None

 

operation selection

1 to 15: Preset speed

c103

Communication time-out

0: Disconnection detection

 

1: When communication mode enable (Both cmod and

 

condition selection

fmod are set CANopen or communication option) only

 

 

2: 1 + Driving operation

c120*

CC-Link station number

1 to 64

 

selection

Set the number of stations of inverters (Remote device

 

 

 

 

station).

c121*

CC-Link baud rate selection

0: 156kbps

 

 

1: 625kbps

 

 

2: 2.5Mbps

 

 

3: 5Mbps

 

 

4: 10Mbps

 

 

Set the baud rate for CC-LINK network

c122*

CC-Link extended selection

0: Occupies one station (V1.10)

 

 

1: Occupies one station double (V2.0)

 

 

2: Occupies one station quadruple (V2.0)

 

 

3: Occupies one station octuple (V2.0)

 

 

The function of remote registers can be enhanced.

* Set parameters according to the CC-Link network system.

- 13 -

Page 14
Image 14
Toshiba E6581830 instruction manual Communication parameters for CCL003Z, C101