E658130
5.5.I/O signal list
5.5.1. One station is occupied (CC-Link Ver.1) (c122=0)
This option occupies one station area of the buffer memory of the PLC.
In the case of c122 = 0, there are remote I/O (RX, RY both 32 bits) and the remote register (RWw, RWr both 4 word) in the communication data for one station area.
Remote I/O (Default value = 0)
Inverter (Slave) → PLC (Master) | PLC (Master) → Inverter (Slave) | |||
Device No. | Signal | Device No. | Signal | |
RXn0 | Forward running | RYn0 | Forward rotation command | |
RXn1 | Reverse running | RYn1 | Reverse rotation command | |
RXn2 | Output terminal 1 | RYn2 | Input terminal 3 (S1) | |
RXn3 | Output terminal 2 (OUT) | RYn3 | Input terminal 4 (S2) | |
RXn4 | Output terminal 3 (FL) | RYn4 | Input terminal 5 (S3) | |
RXn5 | Failure FL | RYn5 | Input terminal 6 (S4) | |
RXn6 | PI control OFF | RYn6 | Input terminal 7 (PIOFF) | |
RXn7 | Acceleration/deceleration | RYn7 | Input terminal 8 (AD1) | |
pattern selection (1 or 2) | ||||
|
|
| ||
RXn8 | Emergency stop | RYn8 | Input terminal 9 (ESTP) | |
RXn9 | Coast stop (ST = OFF) | RYn9 | Intercept output to inverter | |
(Coast stop) | ||||
|
|
| ||
RXnA | Alarm | RYnA | Frequency priority | |
RXnB | Reserved* | RYnB | Command priority | |
RXnC | Monitoring | RYnC | Monitor command | |
RXnD | Frequency setting completion | RYnD | Frequency setting command | |
(RAM) | (RAM) | |||
|
| |||
RXnE | Reserved* | RYnE | Reserved** | |
RXnF | Instruction code execution | RYnF | Instruction code execution request | |
completion | ||||
|
|
| ||
RX(n+1)0 |
| RY(n+1)0 |
| |
to | Reserved* | to | Reserved** | |
RX(n+1)9 |
| RY(n+1)9 |
| |
|
|
| Error reset request flag | |
RX(n+1)A | Error status flag | RY(n+1)A | (A reset request is during switched | |
|
|
| ON) | |
RX(n+1)B | Remote station ready | RY(n+1)B | Reserved** | |
RX(n+1)C |
| RY(n+1)C |
| |
to | Reserved* | to | Reserved** | |
RX(n+1)F |
| RY(n+1)F |
|
"n" is depend on the station number.
*The bit described " Reserved " is unstable. Don't use the “Reserved " bit for the judgment.
**Set OFF (“0”) to reserved bit.
Remote register (Default value = 0)
RWr | Inverter → PLC | RWw | PLC → Inverter |
Address | Signal | Address | Signal |
RWr n | Monitor value 1 | RWw n | Monitor code (1 and 2) |
RWr n+1 | Monitor value 2 | RWw n+1 | Set frequency |
(output frequency) |
|
| |
|
|
| |
RWr n+2 | Reply code | RWw n+2 | Instruction code |
RWr n+3 | Read data | RWw n+3 | Write data |
"n" is depend on the station number.