6.5.Program example for monitoring the output frequency

Example 5 shows a ladder logic to read the output frequency of station 1 inveter to D1. Output frequency reading code number: 0001H (hexadecimal)

When the output frequency is 50Hz, D1 is 1388H (5000) (unit: 0.01Hz).

X0 X0F X1 SW80.0

( M0)

M0 X20

[ MOV H1 W100]

( Y100C)

X100C

[ MOV W1 D1]

[ END]

Check the ready of the station 1

Set monitor code (H0001) of output frequency to RWw0.

Turn on the monitor command (RY0C)

Read output frequency (RWr0) to D1

when the monitoring flag (RX0C) turns on.

Example 5

Refer to 5.5.11 for detail.