E658130

7.Unusual diagnosis

7.1. Option error

The error message is displayed when there is hardware error, software error or lose of connection of wire.

▼Display of trip information

e-23 (Optional unit fault 2 : 0037H) : Option error

7.2. Disconnection error of network cable

▼Display of trip information

err8 (Optional unit fault 1: 001BH): Network error stop

*If a network error occurs when c101 is set to "4", it is displayed.

▼Related parameter

TitleFunction

Setting range

Description

c100

Communication error

0.0 to100.0 sec

detection delay time

c101

Inverter operation at the

0 to 5

 

communications loss action

 

c102

Preset speed operation

0 to 15

 

selection

 

 

 

 

c103

Communication time-out

0 to 2

 

condition selection

 

The waiting time from when a network error occurs can be adjusted. If a network error continues past the time set in c100, it is recognized as a communication error and the operation of the inverter follows the setting of c101.

When normal communication returns during the setting time, a communication error is not displayed and operation is continued.

* Time-out time = CC-Link network time out

+c100

(communication error detection delay time) [0.1s] The operation of the drive when the communication fault occurs can be specified.

The operation frequency of the drive when the communication fault occurs can be specified. (Only when c101 is set to 5)

Select the communication time-out condition.

- 47 -

Page 48
Image 48
Toshiba E6581830 instruction manual Unusual diagnosis, Option error, Disconnection error of network cable