7.3.How to check the error using the LEDs
The following example explains the causes of fault which may be judged from the LED status of the
1. When One Inverter Is Connected
The following example indicates the causes of faults which may be judged from the LED status of the
P
S CPU
Master
Unit
Station
1
inverter
PS: Power supply
| LED Status |
| Cause | Corrective Action | ||
|
|
|
| |||
L.RUN | SD | RD | L.ERR |
|
| |
|
|
|
| Normal communication is | Check that the communication cable is | |
|
|
|
| made but CRC error has | connected to SLD. | |
|
|
|
| occurred due to noise. | Also wire it as far away as possible from | |
● | ● | ● | ◎ |
| the power lines.(200mm or more) | |
|
|
|
| Baud rate or station number | After correcting the baud rate and/ir | |
|
|
|
| was changed during | station number setting, switch power on | |
|
|
|
| operation. | again. | |
● | ● | ● | ○ | Normal communication | - | |
|
|
|
|
|
| |
|
|
|
| Cannot answer due to CRC | Check that the communication cable is | |
● | ○ | ● | ◎ | error of receive data. | connected to SLD. | |
| Also wire it as far away as possible from | |||||
|
|
|
|
| ||
|
|
|
|
| the power lines.(200mm or more) | |
|
|
|
| Data sent to the host station | Check the network transmission setting | |
● | ○ | ● | ○ | does not reach destination. | and the sequence program on the PLC | |
|
|
|
|
| side. | |
|
|
|
| Hardware fault | Check for contact fault, break in the cable, | |
|
|
|
| (There is a possibility of the | etc. | |
● | ○ | ○ | ○ | instability of the |
| |
|
|
|
| communication by the |
| |
|
|
|
| disconnection.) |
| |
|
|
|
| Polling response is made but | Check that the communication cable is | |
○ | ● | ● | ◎ | refresh receive is in CRC | connected to SLD. | |
error. | Also wire it as far away as possible from | |||||
|
|
|
| |||
|
|
|
|
| the power lines.(200mm or more) | |
|
|
|
| Data sent to the host station | Check that the communication cable is | |
○ | ○ | ● | ◎ | is in CRC error. | connected to SLD. | |
| Also wire it as far away as possible from | |||||
|
|
|
|
| ||
|
|
|
|
| the power lines.(200mm or more) | |
|
|
|
| There is no data sent to the | Check that the communication cable is | |
○ | ○ | ● | ○ | host station, or data sent to | connected to SLD. | |
the host station cannot be | Also wire it as far away as possible from | |||||
|
|
|
| |||
|
|
|
| received due to noise. | the power lines.(200mm or more) | |
|
|
|
| Cannot receive data due to | Check for contact fault, break in the cable, | |
|
|
|
| break in the cable, etc. | etc. | |
○ | ○ | ○ | ○ | WDT error occurrence | Check that CCL003Z is fitted properly. | |
|
|
|
| (hardware fault), power off, |
| |
|
|
|
| power supply failure |
| |
|
|
|
| ●:On, ○:OFF, ◎:Flicker, *: Any of on, flicker or off. | ||
|
|
|