E658130

2. Remote register (Inverter -> Master)

RWr

Address

Signal

Description

RWr n

Monitor value 1

When (RYnC) is on, the monitored value specified to the lower 8 bits of

the monitor code (RWwn) is set.

 

 

 

 

When "0" is set to the higher 8 bits of the monitor code (RWwn), the

 

Monitor value 2

current output frequency is always set. When other than "0" is set to the

RWrn+1

upper 8 bits of the monitor code (RWwn) and (RYnC) is on, the

(output frequency)

 

monitored value specified to the higher 8 bits of the monitor code

 

 

 

 

(RWwn) is set.

 

 

When (RYnF) is on, the response code correspond to the instruction

RWrn+2

Response code 1

code of (RWwn+2) is set. The value "0" is set for a normal reply and

 

 

other than "0" is set for data fault, mode error, etc.

RWrn+3

Read data 1

For a normal reply, the reply data to the instruction specified by the

instruction code is set.

 

 

RWrn+4

Monitor value 3

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+4) is set.

 

 

RWrn+5

Monitor value 4

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+5) is set.

 

 

RWrn+6

Monitor value 5

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+6) is set.

 

 

RWrn+7

Monitor value 6

When (RYnC) is on, the monitored value specified to the monitor code

(RWw n+7) is set.

 

 

 

Trip information

The fault data of the trip history No. specified by (RWw n+8) is stored in

RWrn+8

the lower 8bits.

(Trip code)

 

The trip history No. specified is echo backed to the upper 8bits.

 

 

RWrn+9

Trip information

Output frequency of the trip history No. specified in (RWw n+8) is

(output frequency)

stored.

 

RWrn+A

Trip information

Output current of the trip history No. specified in (RWw n+8) is stored.

(output current)

 

 

 

RWrn+B

Trip information

Output voltage of the trip history No. specified in (RWw n+8) is stored.

(output voltage)

 

 

 

RWrn+C

Trip information

Energization time of the trip history No. specified in (RWw n+8) is

(energization time)

stored.

 

RWrn+D

 

Do not use it.

to

Reserved

 

RWrn+F

 

 

 

 

When (RYnF) is on, the response code correspond to the instruction

RWrn+10

Reply code 2

code of (RWw n+10) is set. The value "0" is set for a normal reply and

 

 

other than "0" is set for data fault, mode error, etc.

RWrn+11

Read data 2

For a normal reply, the reply data to the instruction specified by the

instruction code is set.

 

 

 

 

When (RYnF) is on, the response code correspond to the instruction

RWrn+12

Reply code 3

code of (RWw n+12) is set. The value "0" is set for a normal reply and

 

 

other than "0" is set for data fault, mode error, etc.

- 26 -

Page 27
Image 27
Toshiba E6581830 instruction manual Monitor code RWwn is set