Toshiba E6581830 Installation on inverter, Connection cable, Terminating resistor

Models: E6581830

1 51
Download 51 pages 25.25 Kb
Page 8
Image 8

E658130

4. Installation on inverter

Refer to VF-S15 option adapter instruction manual (E6581838) for the installation on the inverter.

Mandatory

The following steps must be performed before installing.

1.Shut off all input power.

2.Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit.

4.1. Connection cable

In the CC-Link system, use CC-Link dedicated cables.

If the cable used is other than the CC-Link dedicated cable, the performance of the CC-Link system is not guaranteed.

For the specifications of the CC-Link dedicated cable, refer to the website of the CC-Link Partner Association.

Website: http://www.cc-link.org/

Strip off the sheath of the CC-Link dedicated cable and wind wires to use. If the length of the sheath pealed is too long, a short circuit may occur among neighboring wires. If the length is too short, wires might come off.

Recommended screwdriverSmall flat-blade screwdriver

(Tip thickness: 0.4mm /tip width: 2.5mm)

Recommented tightening Torque0.22Nm to 0.25Nm

Cable stripping sizeAbout 7mm

mm

*Fix a cable so that a communication connector may be not taken the weight of wire. When the cable is not connected easily, the use of the following bar terminal is recommended.

Phoenix Contact Co. Ltd.

Bar terminal model: AI-TWIN2x0,5-8 WH

Length of bar terminal: 8mm

4.2. Terminating resistor

Connect the terminating resistor of 110Ω or 130Ω (CC-Link Ver.1.00 dedicated high performance cable.) between terminals at the end.

- 7 -

Page 8
Image 8
Toshiba E6581830 instruction manual Installation on inverter, Connection cable, Terminating resistor