E658130
5.Functions
This option is a communication interface unit that allows the PLC program to operate, monitor and set the parameter of the inverter as a remote station of
Moreover, more data transmissions are possible by the use of
5.1. Initial setting
Set the following parameters of the inverter.
Title | Function | Description | Factory | |||
setting | setting | |||||
|
|
|
| |||
|
|
| 0: Terminal board |
|
| |
cmod | Command mode | 1: Panel keypad (including remote keypad) | 1 | 4 | ||
2: RS485 communication | ||||||
| selection |
| ||||
|
| 3: CANopen communication |
|
| ||
|
|
|
|
| ||
|
|
| 4: Communcation option |
|
| |
|
|
| 0: Setting dial 1 (save even if power is off) |
|
| |
|
|
| 1: Terminal board VIA |
|
| |
|
|
| 2: Terminal board VIB |
|
| |
|
|
| 3: Setting dial 2 (press in center to save) |
|
| |
|
|
| 4: RS485 communication |
|
| |
| Frequency | setting | 5: UP/DOWN from external logic input | 0 | 7 | |
fmod | 6: CANopen communication | |||||
mode selection 1 | ||||||
| 7: Communication option |
|
| |||
|
|
|
|
| ||
|
|
| 8: Terminal board VIC |
|
| |
|
|
| 9, 10: - |
|
| |
|
|
| 11: Pulse train input |
|
| |
|
|
| 12, 13: - |
|
| |
|
|
| 14: sro |
|
| |
|
|
| 1: 2 poles |
|
| |
|
|
| 2: 4 poles |
|
| |
| Number of motor | 3: 6 poles |
|
| ||
| 4: 8 poles | 2 | * | |||
f856 | pole for |
| ||||
| 5: 10 poles | |||||
| communication |
|
|
| ||
|
| 6: 12 poles |
|
| ||
|
|
|
|
| ||
|
|
| 7: 14 poles |
|
| |
|
|
| 8: 16 poles |
|
| |
f899 | Communication | 0: - | 0 | - | ||
function reset |
| 1: Reset (after execution: 0) | ||||
|
|
|
|
*Set parameter according to number of motor pole used.