E658130
5.5.8. Instruction Codes
Code No. | Item | Description | ||
1003H | Command mode selection | 0: Terminal block | ||
1: Panel keypad (including extension panel) | ||||
read | ||||
|
| 2: RS485 communication | ||
|
|
| ||
|
| Command mode selection | ||
2003H | 3: No function | |||
write | 4: Communication option | |||
|
| |||
|
|
| 0: Setting dial 1(save even if power is off) | |
|
|
| 1: Terminal VIA | |
1004H | Frequency setting mode | 2: Terminal VIB | ||
selection read | 3: Setting dial 2(press in center to save) | |||
|
| |||
|
|
| 4: RS485 communication | |
|
|
| 5: UP/DOWN from external logic input | |
|
|
| 6: No function | |
|
|
| 7: Communication option | |
|
| Frequency setting mode | 8: Terminal VIC | |
2004H | 9, 10: - | |||
selection write | ||||
|
| 11: Pulse train input | ||
|
|
| ||
|
|
| 12, 13: - | |
|
|
| 14: sro | |
0072H | Special monitor | 0000H to FFFFH: | ||
Monitor value selected after choosing instruction code 00F3H. | ||||
|
|
| ||
read | 0073H | Special monitor code read | Read the content that was monitored by special monitor. | |
write | 00F3H | Special monitor selection | Select the monitor code of special monitor. | |
0074H | Trip history No.1, No.2 read | Read the No.1 and No.2 of trip information. | ||
0075H | Trip history No.3, No.4 read | Read the No.3 and No.4 of trip information. | ||
0076H | Trip history No.5, No.6 read | Read the No.5 and No.6 of trip information. | ||
0077H | Trip history No.7, No.8 read | Read the No.7 and No.8 of trip information. | ||
006DH | Frequency command value | Read the frequency command value (RAM). | ||
(RAM) read | ||||
|
|
| ||
00EDH | Option frequency command | Write the option frequency command value (EEPROM &RAM). | ||
value (EEPROM&RAM) write* | ||||
00F4H | Trip history clear | 9696H: Clear all trip histories. | ||
00FCH | Parameter all clear | 9696H: Clear all parameters. (Parameters other than | ||
proofreading values are made into factory default settings.) | ||||
|
|
| ||
00FDH | Inverter reset | 9696H: Reset the inverter. | ||
|
|
| To read parameters f000 to f984, add the triple figures | |
1000H to 1999H |
| that follow Fxxx to 1000H. | ||
(1000H to | Read parameters (RAM) | (Ex: f984 | ||
1F99H) |
| No error occurs when you select 1A00 to 1F99. | ||
|
|
| Because these parameters are for maintenance. | |
2000H to 2999H | Write parameters | To write parameters f000 to f984, add the triple figures | ||
|
| (EEPROM&RAM) * | that follow Fxxx to 2000H. |
- 28 -