E658130
5.5.4. Octuple setting is selected (CC-Link Ver.2) (c122=3)
This option occupies one station area of the buffer memory of the PLC.
In the case of c122 = 3, there are remote I/O (RX, RY both 32 bits(same as
* Default value of RY and RX is 0.
Remote register (Default value = 0)
RWr | Inverter → PLC | RWw | PLC → Inverter | |||
Address |
| Signal | Address |
| Signal | |
RWr n | Monitor value 1 | RWw n | Monitor code (1 and 2) | |||
RWr n+1 | Monitor value 2 | RWw n+1 | Set frequency |
| ||
(output frequency) |
|
|
|
| ||
|
|
|
|
| ||
RWr n+2 | Reply code |
| RWw n+2 | Instruction code | ||
RWr n+3 | Read data |
| RWw n+3 | Write data |
| |
RWr n+4 | Monitor value 3 | RWw n+4 | Monitor code 3 |
| ||
RWr n+5 | Monitor value 4 | RWw n+5 | Monitor code 4 |
| ||
RWr n+6 | Monitor value 5 | RWw n+6 | Monitor code 5 |
| ||
RWr n+7 | Monitor value 6 | RWw n+7 | Monitor code 6 |
| ||
| Upper 8 | Trip history No. |
| Upper 8 |
| Trip history No.. |
| Bits |
| Bits |
| ||
RWr n+8 |
| RWw n+8 |
|
| ||
Lower 8 | Trip code | Lower 8 |
| Reserved** | ||
|
|
| ||||
| Bits |
| Bits |
| ||
|
|
|
|
| ||
RWr n+9 | Trip information (output frequency) | RWw n+9 | Reserved** |
| ||
RWr n+A | Trip information (output current) | RWw n+A | Reserved** |
| ||
RWr n+B | Trip information (output voltage) | RWw n+B | Reserved** |
| ||
RWr n+C | Trip information (energization time) | RWw n+C | Reserved** |
| ||
RWr n+D | Reserved* |
| RWw n+D | Reserved** |
| |
RWr n+E | Reserved* |
| RWw n+E | Reserved** |
| |
RWr n+F | Reserved* |
| RWw n+F | Reserved** |
| |
RWr n+10 | Reply code 2 |
| RWw n+10 | Instruction code 2 | ||
RWr n+11 | Read data 2 |
| RWw n+11 | Write data 2 |
| |
RWr n+12 | Reply code 3 |
| RWw n+12 | Instruction code 3 | ||
RWr n+13 | Read data 3 |
| RWw n+13 | Write data 3 |
| |
RWr n+14 | Reply code 4 |
| RWw n+14 | Instruction code 4 | ||
RWr n+15 | Read data 4 |
| RWw n+15 | Write data 4 |
| |
RWr n+16 | Reply code 5 |
| RWw n+16 | Instruction code 5 | ||
RWr n+17 | Read data 5 |
| RWw n+17 | Write data 5 |
| |
RWr n+18 | Reply code 6 |
| RWw n+18 | Instruction code 6 | ||
RWr n+19 | Read data 6 |
| RWw n+19 | Write data 6 |
| |
RWr n+1A | Reserved* |
| RWw n+1A | Reserved** |
| |
RWr n+1B | Reserved* |
| RWw n+1B | Reserved** |
| |
RWr n+1C | Reserved* |
| RWw n+1C | Reserved** |
| |
RWr n+1D | Reserved* |
| RWw n+1D | Reserved** |
| |
RWr n+1E | Reserved* |
| RWw n+1E | Reserved** |
| |
RWr n+1F | Reserved* |
| RWw n+1F | Reserved** |
|
"n" is depend on the station number.
*The bit described " Reserved " is unstable. Don't use the “Reserved " bit for the judgment.
**Do not use it.