E658130

5.5.4. Octuple setting is selected (CC-Link Ver.2) (c122=3)

This option occupies one station area of the buffer memory of the PLC.

In the case of c122 = 3, there are remote I/O (RX, RY both 32 bits(same as CC-LINK Ver.1)) and the remote register (RWw, RWr both 32 word) in the communication data for one station area.

* Default value of RY and RX is 0.

Remote register (Default value = 0)

RWr

Inverter → PLC

RWw

PLC → Inverter

Address

 

Signal

Address

 

Signal

RWr n

Monitor value 1

RWw n

Monitor code (1 and 2)

RWr n+1

Monitor value 2

RWw n+1

Set frequency

 

(output frequency)

 

 

 

 

 

 

 

 

 

RWr n+2

Reply code

 

RWw n+2

Instruction code

RWr n+3

Read data

 

RWw n+3

Write data

 

RWr n+4

Monitor value 3

RWw n+4

Monitor code 3

 

RWr n+

Monitor value 4

RWw n+5

Monitor code 4

 

RWr n+

Monitor value 5

RWw n+6

Monitor code 5

 

RWr n+

Monitor value 6

RWw n+7

Monitor code 6

 

 

Upper 8

Trip history No.

 

Upper 8

 

Trip history No..

 

Bits

 

Bits

 

RWr n+8

 

RWw n+8

 

 

Lower 8

Trip code

Lower 8

 

Reserved**

 

 

 

 

Bits

 

Bits

 

 

 

 

 

 

RWr n+9

Trip information (output frequency)

RWw n+9

Reserved**

 

RWr n+A

Trip information (output current)

RWw n+A

Reserved**

 

RWr n+B

Trip information (output voltage)

RWw n+B

Reserved**

 

RWr n+C

Trip information (energization time)

RWw n+C

Reserved**

 

RWr n+D

Reserved*

 

RWw n+D

Reserved**

 

RWr n+E

Reserved*

 

RWw n+E

Reserved**

 

RWr n+F

Reserved*

 

RWw n+F

Reserved**

 

RWr n+10

Reply code 2

 

RWw n+10

Instruction code 2

RWr n+11

Read data 2

 

RWw n+11

Write data 2

 

RWr n+12

Reply code 3

 

RWw n+12

Instruction code 3

RWr n+13

Read data 3

 

RWw n+13

Write data 3

 

RWr n+14

Reply code 4

 

RWw n+14

Instruction code 4

RWr n+1

Read data 4

 

RWw n+15

Write data 4

 

RWr n+1

Reply code 5

 

RWw n+16

Instruction code 5

RWr n+1

Read data 5

 

RWw n+17

Write data 5

 

RWr n+18

Reply code 6

 

RWw n+18

Instruction code 6

RWr n+19

Read data 6

 

RWw n+19

Write data 6

 

RWr n+1A

Reserved*

 

RWw n+1A

Reserved**

 

RWr n+1B

Reserved*

 

RWw n+1B

Reserved**

 

RWr n+1C

Reserved*

 

RWw n+1C

Reserved**

 

RWr n+1D

Reserved*

 

RWw n+1D

Reserved**

 

RWr n+1E

Reserved*

 

RWw n+1E

Reserved**

 

RWr n+1F

Reserved*

 

RWw n+1F

Reserved**

 

"n" is depend on the station number.

*The bit described " Reserved " is unstable. Don't use the “Reserved " bit for the judgment.

**Do not use it.

-19 -

Page 20
Image 20
Toshiba E6581830 instruction manual Octuple setting is selected CC-Link Ver.2 c122=3