Outdoor module - Two units connected

Outdoor module - Two units connected

MMY-AP1401T8, AP1601T8, AP1801T8, AP2001T8, AP2211T8, AP2411T8, MMY-AP1401HT8, AP1601HT8, AP1801HT8, AP2001HT8, AP2211HT8, AP2411HT8,

Notes:

1.If there is an obstacle at the top of the outdoor unit, ensure that the top of the outdoor unit clears the obstacle by 2000 mm.

2. Ensure that the height of obstacles around the outdoor unit does not exced 800 mm from the bottom of the outdoor unit.

3. Draw out the field-supplied pipe to the front of the outdoor unit horizontally, and keep 500 mm or more between the outdoor unit and pipe if placing the pipe transversely.

4.Arrange each outdoor unitin order of its capacity

(Master unit ≥ slave unit)

 

 

 

Unit combination

Outdoor unit combination

 

 

Master unit

Slave unit

MMY-AP1401T8, AP1401HT8

MMY-MAP0801T8, MAP0801HT8

MMY-MAP0601T8, MAP0601HT8

MMY-AP1601T8, AP1601HT8

MMY-MAP0801T8, MAP0801HT8

MMY-MAP0801T8, MAP0801HT8

MMY-AP1801T8, AP1801HT8

MMY-MAP1001T8, MAP1001HT8

MMY-MAP0801T8, MAP0801HT8

MMY-AP2001T8, AP2001HT8

MMY-MAP1001T8, MAP1001HT8

MMY-MAP1001T8, MAP1001HT8

MMY-AP2211T8, AP2211HT8

MMY-MAP1201T8, MAP1201HT8

MMY-MAP1001T8, MAP1001HT8

MMY-AP2411T8, AP2411HT8

MMY-MAP1201T8, MAP1201HT8

MMY-MAP1201T8, MAP1201HT8

 

 

 

 

Note 4

 

 

Note 4

Note 3

Front

Space required for service

Front

 

Note 4

Note 4 Note 3Unit combinationMaster unit

Front Slave unit FrontManual background

Front FrontManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background Front (For work and service)

Legend

1.Anchor bolt pitch

2.(including feet)

3.8-15 x 20 (slot)

All dimensions are given in mm.