Toshiba HFC R-410A manual Technical specifications, Indoor units 4-wayceiling cassettes

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 46
Image 46
9.Technical specifications

9.Technical specifications

Indoor units

4-way ceiling cassettes

Model MMU-AP

 

0091H

0121H

0151H

0181H

0241H

0271H

0301H

0361H

0481H

0561H

Cooling capacity*

kW

2.8

3.6

4.5

5.6

7.1

8.0

9.0

11.2

14.0

16.0

Heating capacity

kW

3.2

4.0

5.0

6.3

8.0

9.0

10.0

12.5

16.0

18.0

Electrical data

 

 

 

 

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

 

Operating current

A

0.17

0.17

0.19

0.21

0.24

0.24

0.35

0.59

0.81

0.83

Power input

kW

0.020

0.020

0.022

0.026

0.032

0.032

0.048

0.070

0.110

0.112

Starting current

A

0.30

0.30

0.33

0.36

0.42

0.42

0.59

0.87

1.23

1.26

Unit appearance

 

Zinc hot dipping steel plate - heat insulating material attached

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

 

 

 

 

Height

mm

256

256

256

256

256

256

256

319

319

319

Width

mm

840

840

840

840

840

840

840

840

840

840

Depth

mm

840

840

840

840

840

840

840

840

840

840

Unit weight

kg

20

20

22

22

23

23

23

28

28

28

Heat exchanger

 

Finned tube

 

 

 

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

 

 

 

Fan type

 

Turbo fan

 

 

 

 

 

 

 

 

 

Fan motor power input

W

60

60

60

60

60

60

60

90

90

90

Air flow

 

 

 

 

 

 

 

 

 

 

 

High

l/s

222

222

258

292

333

333

367

467

567

581

Medium

l/s

203

203

231

256

256

256

308

361

397

422

Low

l/s

189

189

219

222

228

228

236

297

314

342

Air flow

 

 

 

 

 

 

 

 

 

 

 

High

m3/h

800

800

930

1050

1200

1200

1320

1680

2040

2090

Medium

m3/h

730

730

830

920

920

920

1110

1300

1430

1520

Low

m3/h

680

680

790

800

820

820

850

1070

1130

1230

Sound power level (high/medium/low)

dB(A)

43/42/40

43/42/40

44/42/40

45/42/41

47/44/41

47/44/41

50/46/43

53/49/46

57/51/47

58/53/47

Sound pressure level (high/medium/low)**

dB(A)

30/29/27

30/29/27

31/29/27

32/29/28

34/31/28

34/31/28

37/33/30

40/36/33

44/38/34

45/40/34

Air filter

 

Standard long-life filter supplied

 

 

 

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

 

 

 

 

Gas connection diameter

in

3/8

3/8

1/2

1/2

5/8

5/8

5/8

5/8

5/8

5/8

Liquid connection diameter

in

1/4

1/4

1/4

1/4

3/8

3/8

3/8

3/8

3/8

3/8

Drain connection, nom. dia (polyvinyl tube)

in

1

1

1

1

1

1

1

1

1

1

Ceiling panel model number

 

RBC-U21PG (W)-E

 

 

 

 

 

 

 

 

Panel colour

 

Moon white (Munsell/2.5GY 9.0/0.5)

 

 

 

 

 

 

Panel dimensions

 

 

 

 

 

 

 

 

 

 

 

Height

mm

35

35

35

35

35

35

35

35

35

35

Width

mm

950

950

950

950

950

950

950

950

950

950

Depth

mm

950

950

950

950

950

950

950

950

950

950

Panel weight

kg

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.