Toshiba HFC R-410A Cooling/heating capacity characteristics, Cooling capacity calculation method

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 20
Image 20
3. Cooling/heating capacity characteristics

3. Cooling/heating capacity characteristics

Cooling capacity calculation method:

Required cooling capacity = cooling capacity x factor (, , , , *1) kW

Indoor air wet bulb temperature vs. capacity correction value

Capacity correction value

Indoor air wet bulb temperature (°C)

Outdoor air dry bulb temperature vs. capacity correction value

Capacity correction value

Outdoor air dry bulb temperature (°C)

Air flow variation ratio of indoor unit vs. capacity correction (for ducted units only)

Capacity correction value

Air flow variation ratio (%)

*1 Outdoor unit capacity correction factor when total capacity of the indoor units is not equal to the outdoor unit capacity.

20

Page 20
Image 20
Toshiba HFC R-410A manual Cooling/heating capacity characteristics, Cooling capacity calculation method