4. Selection of refrigerant piping
|
|
|
|
| Branching pipe | Header branching pipe |
|
|
|
|
|
| |
Slave | Slave | Slave | Master |
| Indoor unit connection piping | |
unit 3 | unit 2 | unit 1 | unit |
| ||
|
|
| ||||
|
|
|
| Outdoor unit |
|
|
|
|
|
| Balance pipe |
|
|
|
|
|
| Indoor unit | ||
|
|
|
| branching joint |
| |
Outdoor unit |
|
|
| branching |
| |
|
|
|
|
| ||
connection |
|
|
| Main piping | joint |
|
piping |
|
|
|
|
| |
|
|
|
|
|
| |
|
| Main connection |
|
|
| |
|
| piping between | 1st branching | Indoor unit |
| |
|
| outdoor units | section | connection piping |
|
Indoor unit
Pipe size of outdoor unit (Table 1)
Model name | MMY- | Gas side | Liquid side |
MAP0501T8 | MAP0501HT8 | Ø5/8” | Ø3/8” |
MAP0601T8 | MAP0601HT8 | Ø3/4” | Ø3/8” |
MAP0801T8 | MAP0801HT8 | Ø7/8” | Ø1/2” |
MAP1001T8 | MAP1001HT8 | Ø7/8” | Ø1/2” |
MAP1201T8 | MAP1201HT8 | Ø1/2” |
Connecting pipe size between outdoor units (Table 2)
Total capacity code of | Gas side | Liquid side | Balance pipe |
outdoor units downstream |
|
|
|
14 to below 22 | Ø5/8” | Ø3/8” | |
22 to below 26 | Ø5/8” | Ø3/8” | |
26 to below 36 | Ø3/4” | Ø3/8” | |
36 or more | Ø7/8” | Ø3/8” |
Size of main pipe (Table 3)
Total capacity code of | Gas side | Liquid side |
all outdoor units (*1) |
|
|
Below 6 | Ø5/8” | Ø3/8” |
6 to below 8 | Ø3/4” | Ø3/8” |
8 to below 12 | Ø7/8” | Ø1/2” |
12 to below 14 | Ø1/2” | |
14 to below 22 | Ø5/8” | |
22 to below 26 | Ø5/8” | |
26 to below 36 | Ø3/4” | |
36 to below 46 | Ø7/8” | |
46 or more | Ø7/8” |
Determine thickness of the main pipe according to capacity of the outdoor units.
Pipe size between branching sections (Table 4)
Total capacity code of | Gas side | Liquid side |
indoor units downstream (*1) |
|
|
2.8 or less | Ø1/2” | Ø3/8” |
2.8 to below 6.4 | Ø5/8” | Ø3/8” |
6.4 to below 12.2 | Ø7/8” | Ø1/2” |
12.2 to below 20.2 | Ø5/8” | |
20.2 to below 25.2 | Ø5/8” | |
25.2 to below 35.2 | Ø3/4” | |
35.2 or more | Ø7/8” |
If the total capacity code value of indoor units exceeds that of the outdoor units, apply the capacity code of the outdoor units.
Piping of indoor unit (Table 5)
Indoor unit size | Gas side | Liquid side | |
007 to 012 | Actual length 15 m or less | Ø3/8” | Ø1/4” |
| Actual length exceeds 15 m | Ø1/2” | Ø1/4” |
015 to 018 |
| Ø1/2” | Ø1/4” |
024 to 056 |
| Ø5/8” | Ø3/8” |
072 to 096 |
| Ø7/8” | Ø1/2” |
Selection of branching section (Table 6)
|
| Total capacity code of indoor unit (*1) | Model | |
|
| Below 6.4 | ||
branching joint |
| 6.4 to below 14.2 | ||
(*2) |
| 14.2 to below 25.2 | ||
|
|
| 25.2 or more | |
| Branching | For 4 | Below 14.2 | |
header | branching | 14.2 to below 25.2 | ||
(*3) | For 8 | Below 14.2 | ||
|
| branching | 14.2 to below 25.2 | |
| 1 set of 3 types of | |||
branching joint | described below: |
| ||
(For connecting | The required quantity is arranged and |
| ||
outdoor unit) | combined at the site. |
| ||
|
| • Balance pipe (Corresponding difference |
| |
|
| Ø3/8”) × 1 |
| |
|
| • Piping at liquid side (Corresponding |
| |
|
| difference Ø3/8” to Ø7/8”) × 1 |
| |
|
| • Piping at gas side (Corresponding |
| |
|
| difference Ø5/8” to |
|
Minimum wall thickness for
Soft | Half hard or hard | OD (Inch) | Minimum wall thickness (mm) |
OK | OK | 1/4” | 0.80 |
OK | OK | 3/8” | 0.80 |
OK | OK | 1/2” | 0.80 |
OK | OK | 5/8” | 1.00 |
NG | OK (*4) | 3/4” | 1.00 |
NG | OK (*4) | 7/8” | 1.00 |
NG | OK (*4) | 1.00 | |
NG | OK (*4) | 1.10 | |
NG | OK (*4) | 1.25 |
*1 Code is determined according to the unit size. For details, refer to pages
*2 When using
*3 For one line after header branching, indoor units with a maximum of 6.0 capacity code in total can be connected. *4 If the pipe size is Ø3/4” or more, use a hard type or half hard type for material of the pipe.
*5 The maximum equivalent length of the main pipe should be 70 m or shorter.
32