Toshiba HFC R-410A manual Indoor units High-wallunits 1 Series

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 53
Image 53
Indoor units

Indoor units

High-wall units (1 Series)

Model MMK-AP

 

0071H

0091H

0121H

0151H

0181H

0241H

Cooling capacity*

kW

2.2

2.8

3.6

4.5

5.6

7.1

Heating capacity

kW

2.5

3.2

4.0

5.0

6.3

8.0

Electrical data

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

Operating current

A

0.30

0.30

0.30

0.32

0.32

0.35

Power input

kW

0.035

0.035

0.035

0.037

0.037

0.040

Starting current

A

0.36

0.36

0.36

0.42

0.42

0.47

Unit appearance

 

 

 

 

 

 

 

Suction grille and side panel

 

Silky mist (Munsell 1Y 8.9/0.5)

 

 

 

 

Discharge grille

 

City grey (Munsell N6.5)

 

 

 

 

Bottom surface

 

Silky mist (Munsell 1Y 8.9/0.5)

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

Height

mm

368

368

368

368

368

368

Width

mm

895

895

895

1055

1055

1430

Depth

mm

210

210

210

210

210

210

Unit weight

kg

18

18

18

19

19

25

Heat exchanger

 

Finned tube

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

Fan type

 

Tangential fan

 

 

 

 

 

Fan motor power input

W

30

30

30

30

30

30

Air flow

 

 

 

 

 

 

 

High

l/s

167

167

167

217

217

333

Medium

l/s

150

150

150

183

183

283

Low

l/s

133

133

133

167

167

250

Air flow

 

 

 

 

 

 

 

High

m3/h

600

600

600

780

780

1200

Medium

m3/h

540

540

540

660

660

1020

Low

m3/h

480

480

480

600

600

900

Sound power level (high/medium/low)

dB(A)

52/47/44

52/47/44

52/47/44

55/51/48

55/51/48

55/51/48

Sound pressure level (high/medium/low)**

dB(A)

39/34/31

39/34/31

39/34/31

42/38/35

42/38/35

42/38/35

Air filter

 

Standard single filter supplied

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

Gas connection diameter

in

3/8

3/8

3/8

1/2

1/2

5/8

Liquid connection diameter

in

1/4

1/4

1/4

1/4

1/4

3/8

Drain connection, nom. dia (polyvinyl tube)

in

3/4

3/4

3/4

3/4

3/4

3/4

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main

piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

53

Page 53
Image 53
Toshiba HFC R-410A manual Indoor units High-wallunits 1 Series