Outdoor units (combination)

Rating

hp

24

 

 

 

24

 

Cooling only system MMY

 

AP2401T8

 

 

 

AP2411T8

 

Heat pump system MMY

 

AP2401HT8

 

 

 

AP2411HT8

 

Outdoor unit type

 

Inverter

Inverter

Inverter

Inverter

Inverter

Outdoor unit combination

 

 

 

 

 

 

 

cooling only MMY-MAP

 

0801T8

0801T8

0801T8

1201T8

1201T8

Outdoor unit combination

 

 

 

 

 

 

 

heat pump MMY-MAP

 

0801HT8

0801HT8

0801HT8

1201HT8

1201HT8

Cooling capacity

kW

68.0

 

 

 

68.0

 

Heating capacity

kW

76.5

 

 

 

76.5

 

Power supply

V-ph-Hz

400-3-50 ± 10%

400-3-50 ± 10%

400-3-50 ± 10%

 

400-3-50 ± 10%

400-3-50 ± 10%

Voltage range

V

380-415

380-415

380-415

 

380-415

380-415

Power input, cooling

kW

18.44

 

 

 

25.02

 

Power factor, cooling

%

96

 

 

 

95

 

Operating current, cooling

A

27.73

 

 

 

38.02

 

EER, cooling

kW/kW

3.69

 

 

 

2.72

 

Starting current

A

1.0

 

 

 

1.0

 

Power input, heating

kW

18.79

 

 

 

21.32

 

Power factor, heating

%

97

 

 

 

96

 

Operating current, heating

A

27.96

 

 

 

32.06

 

COP, heating

kW/kW

4.07

 

 

 

3.59

 

Starting current

A

1.0

 

 

 

1.0

 

Unit appearance

 

Silky shade (Munsell 1Y8.5/0.5)

 

 

 

 

Dimensions

 

 

 

 

 

 

 

Height

mm

1800

1800

1800

 

1800

1800

Width

mm

990

990

990

 

990

990

Depth

mm

750

750

750

 

750

750

Total weight - cooling only unit

kg

256

256

256

 

256

256

Total weight - heat pump unit

kg

258

258

258

 

258

258

Heat exchanger

 

Finned type

 

 

 

 

 

Sound power level

dB(A)

75.0

 

 

 

75.0

 

Sound pressure level

dB(A) at 1 m

62.0

 

 

 

62.0

 

Fan type

 

Propeller

Propeller

Propeller

 

Propeller

Propeller

Motor power input

kW

0.6

0.6

0.6

 

0.6

0.6

Air flow

l/s

2750

2750

2750

 

2917

2917

 

m3/h

9900

9900

9900

 

10500

10500

Compressor type

 

Hermetic

Hermetic

Hermetic

 

Hermetic

Hermetic

Motor power input

kW

2.3 x 2

2.3 x 2

2.3 x 2

 

4.2 x 2

4.2 x 2

Refrigerant charge R-410A*

 

 

 

 

 

 

 

Cooling

kg

11.0

11.0

11.0

 

11.0

11.0

Heating

kg

12.5

12.5

12.5

 

12.5

12.5

Pipework**

 

 

 

 

 

 

 

Suction line type - diameter

in

Brazed - 7/8

Brazed - 7/8

Brazed - 7/8

 

Brazed - 1-1/8

Brazed -1-1/8

Liquid line type - diameter

in

Flare - 1/2

Flare - 1/2

Flare - 1/2

 

Flare - 1/2

Flare - 1/2

Balance pipe type - diameter

in

Flare - 3/8

Flare - 3/8

Flare - 3/8

 

Flare - 3/8

Flare - 3/8

Maximum equivalent length separation

m

175

175

175

 

175

175

Maximum actual piping length

m

150 (if equivalent bend length is longer, equivalent length is standard)

 

Maximum total piping length

m

300

300

300

 

300

300

 

Maximum lift - indoor unit above/below***

m

40/50

40/50

40/50

 

40/50

40/50

Control wiring

 

Shielded wire 1.25 mm2 x 2 cores up to 2000 m

 

 

Central remote controller

 

Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m

 

Max. number of connectable indoor units

 

40

 

 

 

40

 

High-pressure switch

MPa

Off: 2.90/On: 3.73

 

 

 

 

 

Protection devices

 

Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,

 

 

high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,

 

 

 

overcurrent relay

 

 

 

 

 

Operating range, cooling†

°C

-5 to 43 db

-5 to 43 db

-5 to 43 db

 

-5 to 43 db

-5 to 43 db

Operating range, heating†

°C

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

 

-20 to 16 wb

-20 to 16 wb

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.

*The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.

** The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.

*** If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.

† Please refer to page 24.