Outdoor units (combination)
Rating | hp | 24 |
|
|
| 24 |
|
Cooling only system MMY |
| AP2401T8 |
|
|
| AP2411T8 |
|
Heat pump system MMY |
| AP2401HT8 |
|
|
| AP2411HT8 |
|
Outdoor unit type |
| Inverter | Inverter | Inverter | Inverter | Inverter | |
Outdoor unit combination |
|
|
|
|
|
|
|
cooling only |
| 0801T8 | 0801T8 | 0801T8 | 1201T8 | 1201T8 | |
Outdoor unit combination |
|
|
|
|
|
|
|
heat pump |
| 0801HT8 | 0801HT8 | 0801HT8 | 1201HT8 | 1201HT8 | |
Cooling capacity | kW | 68.0 |
|
|
| 68.0 |
|
Heating capacity | kW | 76.5 |
|
|
| 76.5 |
|
Power supply |
| ||||||
Voltage range | V |
| |||||
Power input, cooling | kW | 18.44 |
|
|
| 25.02 |
|
Power factor, cooling | % | 96 |
|
|
| 95 |
|
Operating current, cooling | A | 27.73 |
|
|
| 38.02 |
|
EER, cooling | kW/kW | 3.69 |
|
|
| 2.72 |
|
Starting current | A | 1.0 |
|
|
| 1.0 |
|
Power input, heating | kW | 18.79 |
|
|
| 21.32 |
|
Power factor, heating | % | 97 |
|
|
| 96 |
|
Operating current, heating | A | 27.96 |
|
|
| 32.06 |
|
COP, heating | kW/kW | 4.07 |
|
|
| 3.59 |
|
Starting current | A | 1.0 |
|
|
| 1.0 |
|
Unit appearance |
| Silky shade (Munsell 1Y8.5/0.5) |
|
|
|
| |
Dimensions |
|
|
|
|
|
|
|
Height | mm | 1800 | 1800 | 1800 |
| 1800 | 1800 |
Width | mm | 990 | 990 | 990 |
| 990 | 990 |
Depth | mm | 750 | 750 | 750 |
| 750 | 750 |
Total weight - cooling only unit | kg | 256 | 256 | 256 |
| 256 | 256 |
Total weight - heat pump unit | kg | 258 | 258 | 258 |
| 258 | 258 |
Heat exchanger |
| Finned type |
|
|
|
|
|
Sound power level | dB(A) | 75.0 |
|
|
| 75.0 |
|
Sound pressure level | dB(A) at 1 m | 62.0 |
|
|
| 62.0 |
|
Fan type |
| Propeller | Propeller | Propeller |
| Propeller | Propeller |
Motor power input | kW | 0.6 | 0.6 | 0.6 |
| 0.6 | 0.6 |
Air flow | l/s | 2750 | 2750 | 2750 |
| 2917 | 2917 |
| m3/h | 9900 | 9900 | 9900 |
| 10500 | 10500 |
Compressor type |
| Hermetic | Hermetic | Hermetic |
| Hermetic | Hermetic |
Motor power input | kW | 2.3 x 2 | 2.3 x 2 | 2.3 x 2 |
| 4.2 x 2 | 4.2 x 2 |
Refrigerant charge |
|
|
|
|
|
|
|
Cooling | kg | 11.0 | 11.0 | 11.0 |
| 11.0 | 11.0 |
Heating | kg | 12.5 | 12.5 | 12.5 |
| 12.5 | 12.5 |
Pipework** |
|
|
|
|
|
|
|
Suction line type - diameter | in | Brazed - 7/8 | Brazed - 7/8 | Brazed - 7/8 |
| Brazed - | Brazed |
Liquid line type - diameter | in | Flare - 1/2 | Flare - 1/2 | Flare - 1/2 |
| Flare - 1/2 | Flare - 1/2 |
Balance pipe type - diameter | in | Flare - 3/8 | Flare - 3/8 | Flare - 3/8 |
| Flare - 3/8 | Flare - 3/8 |
Maximum equivalent length separation | m | 175 | 175 | 175 |
| 175 | 175 |
Maximum actual piping length | m | 150 (if equivalent bend length is longer, equivalent length is standard) |
| ||||
Maximum total piping length | m | 300 | 300 | 300 |
| 300 | 300 |
| |||||||
Maximum lift - indoor unit above/below*** | m | 40/50 | 40/50 | 40/50 |
| 40/50 | 40/50 |
Control wiring |
| Shielded wire 1.25 mm2 x 2 cores up to 2000 m |
|
| |||
Central remote controller |
| Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m |
| ||||
Max. number of connectable indoor units |
| 40 |
|
|
| 40 |
|
MPa | Off: 2.90/On: 3.73 |
|
|
|
|
| |
Protection devices |
| Discharge temperature sensor, suction temperature sensor, compressor crankcase heater, | |||||
|
|
| |||||
|
| overcurrent relay |
|
|
|
|
|
Operating range, cooling† | °C |
| |||||
Operating range, heating† | °C |
|
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
*The amount does not cover extra piping lengths. Refrigerant must be added
** The maximum total piping length is the sum of
*** If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
† Please refer to page 24.
61