Toshiba HFC R-410A manual Outdoor module

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 100
Image 100
Outdoor module

Outdoor module

MMY-MAP0501T8, MAP0601T8, MAP0801T8, MAP1001T8, MAP1201T8, MMY-MAP0501HT8, MAP0601HT8, MAP0801HT8, MAP1001HT8, MAP1201HT8,

MMY-MAP0501T8

MMY-MAP0601T8

MMY-MAP0501HT8

MMY-MAP0601HT8

Details of front pipe/cabling holes

Notes:

1. If there is an obstacle at the top of the outdoor unit, ensure that the top of the outdoor unit clears the obstacle by 2000 mm.

2. Ensure that the height of obstacles around the outdoor unit does not exced 800 mm from the bottom of the outdoor unit.

3. Draw out the field-supplied pipe to the front of the outdoor unit horizontally, and keep 500 mm or more between the outdoor unit and pipe if placing the pipe transversely.

Model

A

B

C

MMY-MAP0501T8, MAP0501HT8

5/8”

3/8”

280

MMY-MAP0601T8, MAP0601HT8

3/4”

3/8”

280

MMY-MAP0801T8, MAP0801HT8

7/8”

1/2”

(205)

MMY-MAP1001T8, MAP1001HT8

7/8”

1/2”

(205)

MMY-MAP1201T8, MAP1201HT8

1-1/8”

1/2”

(205)

*1 Cutting position of L-shape pipe when pipe is connected at the gas side. (Recommended pipe connection position)

Space required for service

Front (for work and service)

3

Front

3

Front

Note

Note

 

 

Front

Details of hole for bottom piping (plane view)

Legend

1.Anchor bolt pitch

2.(including feet)

3.4-15 x 20 (slot)

4.2-60 x 150 square hole (for forklift truck)

5.Balance pipe connection Ø3/8”

6.Refrigerant pipe connection (liquid ØB)

7.Refrigerant pipe connection (gas ØA)

8.Earthing section of bottom plate

9.Base

10.Knockout for control wiring (Ø27)

11.Knockout hole for power wiring (Ø48)

12.Square hole

All dimensions are given in mm.

100

Page 100
Image 100
Toshiba HFC R-410A manual Outdoor module