Indoor units

High-wall units (2 Series)

Model MMK-AP

 

0072H

0092H

0122H

Cooling capacity*

kW

2,2

2,8

3,6

Heating capacity

kW

2,5

3,2

4,0

Electrical data

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

Operating current

A

0,17

0,18

0,19

Power input

kW

0,017

0,018

0,019

Starting current

A

0,22

0,23

0,24

Unit appearance

 

 

 

 

Suction grille and side panel

 

Moon white

 

 

Discharge grille

 

Moon white

 

 

Bottom surface

 

Moon white

 

 

Unit dimensions

 

 

 

 

Height

mm

275

275

275

Width

mm

790

790

790

Depth

mm

208

208

208

Unit weight

kg

11

11

11

Heat exchanger

 

Finned tube

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

Fan type

 

Tangential fan

 

 

Fan motor power input

W

30

30

30

Air flow

 

 

 

 

High

l/s

133

142

150

Medium

l/s

117

125

125

Low

l/s

100

100

100

Air flow

 

 

 

 

High

m3/h

480

510

540

Medium

m3/h

420

450

450

Low

m3/h

360

360

360

Sound power level (high/medium/low)

dB(A)

48/45/42

49/46/42

50/46/42

Sound pressure level (high/medium/low)**

dB(A)

35/32/29

36/33/29

37/33/29

Air filter

 

Standard single filter supplied

 

 

Controller

 

Remote controller

 

 

Connection pipes

 

 

 

 

Gas connection diameter

in

3/8

3/8

3/8

Liquid connection diameter

in

1/4

1/4

1/4

Drain connection, nom. dia (polyvinyl tube)

mm

16

16

16

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main

piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

54

Page 54
Image 54
Toshiba HFC R-410A manual Indoor units High-wall units 2 Series