Toshiba HFC R-410A manual Outdoor units

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 58
Image 58
Outdoor units

Outdoor units

Rating

hp

5

6

8

10

12

Cooling only model MMY

 

MAP0501T8

MAP0601T8

MAP0801T8

MAP1001T8

MAP1201T8

Heat pump model MMY

 

MAP0501HT8

MAP0601HT8

MAP0801HT8

MAP1001HT8

MAP1201HT8

Outdoor unit type

 

Inverter

Inverter

Inverter

Inverter

Inverter

Cooling capacity

kW

14.0

16.0

22.4

28.0

33.5

Heating capacity

kW

16.0

18.0

25.0

31.5

37.5

Power supply

V-ph-Hz

400-3-50 ± 10%

400-3-50 ± 10%

400-3-50 ± 10%

400-3-50 ± 10%

400-3-50 ± 10%

Voltage range

V

380-415

380-415

380-415

380-415

380-415

Power input, cooling

kW

3.65

4.64

5.67

7.68

11.92

Power factor, cooling

%

90

92

95

96

94

Operating current, cooling

A

5.85

7.28

8.62

11.55

18.30

EER, cooling

kW/kW

3.84

3.45

3.95

3.65

2.81

Starting current

A

1.0

1.0

1.0

1.0

1.0

Power input, heating

kW

3.84

4.56

5.88

7.97

10.19

Power factor, heating

%

91

93

95

96

94

Operating current, heating

A

6.09

7.08

8.93

11.98

15.65

COP, heating

kW/kW

4.17

3.95

4.25

3.95

3.68

Starting current

A

1.0

1.0

1.0

1.0

1.0

Unit appearance

 

Silky shade (Munsell 1Y8.5/0.5)

 

 

 

Dimensions

 

 

 

 

 

 

Height

mm

1800

1800

1800

1800

1800

Width

mm

990

990

990

990

990

Depth

mm

750

750

750

750

750

Total weight - cooling only unit

kg

227

227

256

256

256

Total weight - heat pump unit

kg

228

228

258

258

258

Heat exchanger

 

Finned type

 

 

 

 

Sound power level

dB(A)

68

69

70

71

72

Sound pressure level

dB(A) at 1 m

55

56

57

58

59

Fan type

 

Propeller

Propeller

Propeller

Propeller

Propeller

Motor power input

kW

0.6

0.6

0.6

0.6

0.6

Air flow

l/s - m3/h

2500 - 9000

2500 - 9000

2750 - 9900

2917 - 10500

2917 - 10500

Compressor type

 

Hermetic

Hermetic

Hermetic

Hermetic

Hermetic

Motor power input

kW

1.1 x 2

1.4 x 2

2.3 x 2

3.1 x 2

4.2 x 2

Refrigerant charge R-410A*

 

 

 

 

 

 

Cooling

kg

8.0

8.0

11.0

11.0

11.0

Heating

kg

8.5

8.5

12.5

12.5

12.5

Pipework**

 

 

 

 

 

 

Suction line type - diameter

in

Flare - 5/8

Brazed - 3/4

Brazed - 7/8

Brazed - 7/8

Brazed - 1-1/8

Liquid line type - diameter

in

Flare - 3/8

Flare - 3/8

Flare - 1/2

Flare - 1/2

Flare - 1/2

Balance pipe type - diameter

in

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Maximum equivalent length separation

m

175

175

175

175

175

Maximum actual piping length

m

150 (if equivalent bend length is longer,

equivalent length is

standard)

 

Maximum total piping length

m

300

300

300

300

300

Maximum lift - indoor unit above/below***

m

40/50

40/50

40/50

40/50

40/50

Control wiring

 

Shielded wire 1.25 mm2 x 2 cores up to

2000 m

 

 

Central remote controller

 

Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m

Max. number of connectable indoor units

 

8

10

13

16

20

High-pressure switch

MPa

Off: 2.90/On: 3.73

 

 

 

 

Protection devices

 

Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,

 

 

high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,

 

 

overcurrent relay

 

 

 

 

Operating range, cooling†

°C

-5 to 43 db

-5 to 43 db

-5 to 43 db

-5 to 43 db

-5 to 43 db

Operating range, heating†

°C

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.

*The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.

** The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.

*** If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.

† Please refer to page 24.

58

Page 58
Image 58
Toshiba HFC R-410A manual Outdoor units