Toshiba HFC R-410A manual Indoor units Floor-mountedconsole units

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 55
Image 55
Indoor units

Indoor units

Floor-mounted console units

Model MML-AP

 

0071H

0091H

0121H

0151H

0181H

0241H

Cooling capacity*

kW

2.2

2.8

3.6

4.5

5.6

7.1

Heating capacity

kW

2.5

3.2

4.0

5.0

6.3

8.0

Electrical data

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

Operating current

A

0.26

0.26

0.43

0.43

0.47

0.47

Power input

kW

0.056

0.056

0.092

0.092

0.102

0.102

Power factor

%

94

94

93

93

94

94

Starting current

A

0.60

0.60

0.80

0.80

1.10

1.10

Unit appearance

 

Silky shade (Munsell 1Y 8.5/0.5)

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

Height

mm

630

630

630

630

630

630

Width

mm

950

950

950

950

950

950

Depth

mm

230

230

230

230

230

230

Unit weight

kg

37

37

37

37

40

40

Heat exchanger

 

Finned tube

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

Fan type

 

Centrifugal fan

 

 

 

 

 

Fan motor power input

W

45

45

45

45

70

70

Air flow

 

 

 

 

 

 

 

High

l/s

133

133

250

250

300

300

Medium

l/s

117

117

217

217

258

258

Low

l/s

100

100

181

181

217

217

Air flow

 

 

 

 

 

 

 

High

m3/h

480

480

900

900

1080

1080

Medium

m3/h

420

420

780

780

930

930

Low

m3/h

360

360

650

650

780

780

Sound power level (high/medium/low)

dB(A)

52/50/48

52/50/48

58/54/51

58/54/51

62/57/52

62/57/52

Sound pressure level (high/medium/low)**

dB(A)

39/37/35

39/37/35

45/41/38

45/41/38

49/44/39

49/44/39

Air filter

 

Standard single filter supplied

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

Gas connection diameter

in

3/8

3/8

3/8

1/2

1/2

5/8

Liquid connection diameter

in

1/4

1/4

1/4

1/4

1/4

3/8

Drain connection, nom. dia (polyvinyl tube)

in

3/4

3/4

3/4

3/4

3/4

3/4

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

55

Page 55
Image 55
Toshiba HFC R-410A manual Indoor units Floor-mountedconsole units